SAUTER flexotron®400 - RDT410
Clock and scheduler
P100012103
27
Should you want the comfort period on Friday to run on until 23:30 you can set
the fourth on-time to day 5 and 23:30 and the fourth off-time to day 5 and 21:01.
The 1 minute dip will not be noticable.
Menu 0.9, Setback
After the eight switching point menus there is a ninth, 0.9. In this menu you set
the number of degrees you wish to lower the room temperature setpoint during
the economy periods. If no room sensor is connected the supply water setpoint
will be lowered by 3 times the set value.
Menu OK
After the scheduler menus there is a final menu, OK. A klick on the encoder knob
will exit the Clock and Scheduler level and return you to the Basic Display.