SAUTER flexotron®400 - RDT410
Configuration
P100012103
28
10 Configuration
All the configuration menus lie in the 10-seconds level. This level is accessed
from the Base Display by clicking and holding the encoder knob for 10 seconds.
There are numerous configuration menus covering all available options and
combinations. In some cases, making a certain choice in one menu will mean
that you will only see certain other menus. For example, the menu for setting the
damper minimum limit is only shown if you have configured AO2 to be a damper
control output.
Menus 1.0
– 5.0
In the first set of configuration menus you choose which of the five control modes
you wish to run. The displayed symbol and the first digit in the menu-number
show which control mode is at hand
Menus X.1
Output type (control modes 1, 2, 3 and 4) (where X depends on
your choice of alternative above)
For control modes 1,2, 3 an
d 4 you can, instead of the 0…10 V analogue output,
choose to use two digital outputs to control a 3-point (increase/decrease)
actuator. In this case DO1 will always be increase (open valve) and DO2
decrease (close valve).
In cont
rolmode 5 you can only have 0…10 V analogue output.
Menu X.A
If 3-point control has been configured, a submenu will be shown in which you set
the actuator run time. The RDT410 uses this value to calculate the run time
needed to achieve a certain desired output.
Menus X.2 Output signals (control modes 1, 2, 3)
Here you choose the combination of output signals.
If you in the preceding menu have chosen analogue 0…10 V outputs, they can
be configured to the following combinations: