SAUTER flexotron®400 - RDT410
Technical data
P100012103
8
Outputs
AO ......................................................
0…10 V DC; 8 bit D/A short-circuit protected
DO1 and DO2 (RDT410F201) ........... Triac controlled, 24 V AC, 0.3 A continuous
(connected to G0)
DO1 and DO2 (RDT410F301) .. Triac controlled, 24 V AC, 0.16 A continuous with
internal trafo (connected to G0)
DO3 .............................................. Change-over (SPDT) relay 230 V AC, 1000 VA
GDO................................................. Reference for DO1 and DO2. 24 V AC output
Other data
Display ............................................... Numeric / graphic. Background illumination.
Setpoints
Range
Factory setting
Temperature
supply air
room
tap hot water
External setpoint
10...80°C
10...50°C
10…80°C
0…40°C
21°C
21°C
55°C
P-band
0…99°C
15°C
I-time
0…990 s
60 s
D-factor
0…99
0
Cascade factor
0…99
2
Minimum at cascade
0…99°C
15
Maximum at cascade
0…99°C
25
Damper minimum limit
0…99
10
Start of outdoor compensation
-
30…50°C
10°C
Outdoor compensation at -20°C outdoor
temp
-
10…10°C
5°C
Supply temperature (water-heated
radiator heating)
at -20°C outdoor temperature
at 20°C outdoor temperature
0…99°C
0…99°C
60°C
20°C
Frost protection
7°C (fixed)
Shutdown mode
25°C
(fixed)
Accessories
Temperature sensors ................... Ni1000 sensors, for example:EGT330, EGT346
Setpoint device ..................................................................... Ni1000, EGT338F102
The accessories are available from Fr. Sauter AG. For more detailed information,
see product sheets and instructions which are available at http://www.sauter-
controls.com/en.