EQJW145: Heating controller
Commissioning
7010015003 A
23
© Fr. Sauter AG
Parameter
Description
Range
Step value
SP34
1
Functions for DHW
0 = not enabled.
1 = MOD 1, 2: with sep. charge pump using one
DHW sensor
2 = MOD 1, 2: with sep. charge pump using two
DHW sensors
3 = MOD 1, 2: with diverter valve using one DHW
sensor
4 = MOD 1, 2: with diverter valve using two DHW
sensors
0…4
1
SP35
60
Maximum setpoint for domestic hot water temp./[°C]
10…70
1
SP36
5
MOD 1, 2: switching difference for DHW in K
1...30
1
SP37
70
Maximum setpoint for increased DHW temperature/[°C]
10…90
1
SP38
10
Setpoint boost for domestic hot water in K
0…30
1
SP39
-30
Outdoor temperature limit value for operation of domestic hot water
heating in °C
TA < limit value parallel operation
TA > limit value domestic hot water with priority
Note: only valid if value SP34 = 1 or 2
-30…50
1
SP40
4
After-run time for charge pump for domestic hot water/[min]
0…20
1
SP41
1.4
Slope of heating characteristic
0.2...5.0
0.1
SP42
10
Setpoint boost for demand request via device bus/ [ K]
0…30
1
SP43
0.0
External heat portion/[K]
0.0...5.0
0.1
SP44
15
Heating limit/[°C]
0...39
1
SP45
1
Outdoor temperature recording for heating limit
0 = TA used unsmoothed for heating limit function
1 = smoothed TA is used for heating limit function
0…1
1
SP46
-16
Design temperature/[°C]
-30...0
1
SP47
2
After-run factor for heating medium pump (after-run time = runtime for
final control element x after-run factor)
1…10
1
SP48
1
Anti-frost function
0 = not enabled
1 = enabled
0...1
1
Summary of Contents for EQJW145
Page 1: ...EQJW145 Heating controller Operating manual 7010015003 A R ...
Page 8: ...EQJW145 Heating controller Symbols used in this manual 8 7010015003 A Fr Sauter AG ...
Page 10: ...EQJW145 Heating controller General information 10 7010015003 A Fr Sauter AG ...
Page 46: ...EQJW145 Heating controller Commissioning 46 7010015003 A Fr Sauter AG ...
Page 78: ...EQJW145 Heating controller Communication functions 78 7010015003 A Fr Sauter AG ...
Page 82: ...EQJW145 Heating controller Faults 82 7010015003 A Fr Sauter AG ...
Page 90: ...EQJW145 Heating controller Economy tips 90 7010015003 A Fr Sauter AG ...
Page 94: ...EQJW145 Heating controller Dimension drawing 94 7010015003 A Fr Sauter AG ...
Page 100: ...EQJW145 Heating controller Technical data 100 7010015003 A Fr Sauter AG ...