EQJW145: Heating controller
Commissioning
22
7010015003 A
© Fr. Sauter AG
Parameter
Description
Range
Step value
SP12
0
Correction to outdoor temperature TA in K
-10.0…+10.0
0.1
SP13
0
Return temperature recording
0 = return temperature is not recorded
1 = return temperature is recorded
0…1
1
SP14
0
Correction to return temperature TRF (MOD3: TRF of heating circuit)
-10.0…+10.0
0.1
SP15
40
Proportional band, PI controller in K
2...100
1
SP16
40
MOD3: Proportional band, PI controller in K (2nd control circuit)
2...100
1
SP17
240
Reset time, PI controller in sec
5...1000
5
SP18
240
MOD3: Reset time, PI controller in sec (2nd control circuit)
5...1000
5
SP19
120
Runtime for final control element in sec
30...960
15
SP20
180
Runtime for second final control element in sec
MOD1, 2: for diverter valve (SP34 = 3 or 4)
MOD3: for second control valve
30...960
15
SP21
5
Minimum limitation for flow temperature TF (heating circuit) in °C
5 …100
1
SP22
75
Maximum limitation for flow temperature TF (heating circuit) in °C
20…150
1
SP23
90
Upper limit value for max. limitation of TRF during heating
in °C
5…150
1
SP24
90
Lower limit value for max. limitation of TRF during heating in °C
5…150
1
SP25
0
Outdoor temperature at which the sliding part of the limit function for
TRF begins, in °C
-30...+50
1
SP26
1.0
Slope of limitation function for TRF in [K/K]
0.0…5.0
0.1
SP27
90
Maximum limitation for return temperature TRF during DHW
heating in °C
5…150
1
SP28
5
Intervention intensity if limit value for return temperature is violated in
[K/K]
0.1…10
0.1
SP29
no
Limit value pulse/min for max. flow or power of heating and DHW
no 0.1...16.0.
60...16000
0.1/1/10
SP30
no
Limit value pulse/min for max. flow or power of heating only
no 0.1...16.0.
60...16000
0.1/1/10
SP31
no
Limit value pulse/min for max. flow or power of DHW only
no 0.1...16.0.
60...16000
0.1/1/10
SP32
0.0
Intervention intensity in K/min if limit value for flow or power is violated
0.0…30.0
0.1
SP33
no
Limit value pulse/min for min. flow or power
no. 0.1...16.0.
60...16000
0.1/1/10
Summary of Contents for EQJW145
Page 1: ...EQJW145 Heating controller Operating manual 7010015003 A R ...
Page 8: ...EQJW145 Heating controller Symbols used in this manual 8 7010015003 A Fr Sauter AG ...
Page 10: ...EQJW145 Heating controller General information 10 7010015003 A Fr Sauter AG ...
Page 46: ...EQJW145 Heating controller Commissioning 46 7010015003 A Fr Sauter AG ...
Page 78: ...EQJW145 Heating controller Communication functions 78 7010015003 A Fr Sauter AG ...
Page 82: ...EQJW145 Heating controller Faults 82 7010015003 A Fr Sauter AG ...
Page 90: ...EQJW145 Heating controller Economy tips 90 7010015003 A Fr Sauter AG ...
Page 94: ...EQJW145 Heating controller Dimension drawing 94 7010015003 A Fr Sauter AG ...
Page 100: ...EQJW145 Heating controller Technical data 100 7010015003 A Fr Sauter AG ...