EQJW145: Heating controller
Commissioning
40
7010015003 A
© Fr. Sauter AG
3.4.4
List of communication parameters
Parameter
Description
Range
Step-
value
CP01
Internal serial number of EQJW 145 (read only)
–
CP02
2
Type of communication
0 = no communication
1 = device bus
2 = MOD bus via RS485
3 = MOD bus via modem
4 = SMS via modem
5 = MOD Bus and SMS via Modem
0…5
1
CP03
19200
Baud rate
9600, 19200
–
CP04
–
Device bus: address EQJW 145
1…32, auto
1
CP05
–
MOD bus via RS485: address EQJW 145
1…247
1
CP06
–
MOD bus via modem: phone number of the control station
–
1
CP07
–
SMS via modem: telephone number of the provider (TAP protocol)
–
1
CP08
–
SMS via modem: telephone number of the mobile phone
–
1
CP09
0
Device bus: time synchronisation
0 = not enabled. 1 = enabled
0…1
1
CP10
0
Device bus: send outdoor temperature
0 = not enabled. 1 = enabled
0…1
1
CP11
0
Device bus: receive outdoor temperature
0 = not enabled. 1 = enabled
0…1
1
CP12
0
Device bus: send heat requirement (TF)
0 = not enabled. 1 = enabled
0…1
1
CP13
0
Device bus: receive heat requirement (TF)
0 = not enabled. 1 = enabled
0…1
1
CP14
0
Device bus: send return temperature
0 = not enabled. 1 = enabled
0…1
1
CP15
0
Device bus: receive return temperature
0 = not enabled. 1 = enabled
0…1
1
CP16
0
Device bus: send error
0 = not enabled. 1 = enabled
0…1
1
CP17
0
Device bus: receive error
0 = not enabled. 1 = enabled
0…1
1
CP18
0
Device bus: EDB 100 digital room operating unit
0 = EDB 100 not connected,
1 = EDB 100 connected
0…1
1
Summary of Contents for EQJW145
Page 1: ...EQJW145 Heating controller Operating manual 7010015003 A R ...
Page 8: ...EQJW145 Heating controller Symbols used in this manual 8 7010015003 A Fr Sauter AG ...
Page 10: ...EQJW145 Heating controller General information 10 7010015003 A Fr Sauter AG ...
Page 46: ...EQJW145 Heating controller Commissioning 46 7010015003 A Fr Sauter AG ...
Page 78: ...EQJW145 Heating controller Communication functions 78 7010015003 A Fr Sauter AG ...
Page 82: ...EQJW145 Heating controller Faults 82 7010015003 A Fr Sauter AG ...
Page 90: ...EQJW145 Heating controller Economy tips 90 7010015003 A Fr Sauter AG ...
Page 94: ...EQJW145 Heating controller Dimension drawing 94 7010015003 A Fr Sauter AG ...
Page 100: ...EQJW145 Heating controller Technical data 100 7010015003 A Fr Sauter AG ...