EQJW145: Heating controller
Communication functions
7010015003 A
73
© Fr. Sauter AG
For the other control loops or the program for the pilot timer/circulation pump,
the same logic applies, but the register numbers are 100 higher in each case.
Every possible switching command has its own holding register (a 16-bit
value) that can be read or written. For the contents of the register, the
following applies:
Command
Time
Numerical
value
(decimal)
3
0
7
3
0
30730
1 = Stand-by mode
2 = Reduced mode
3 = Normal mode
To change the factory setting for the first switching command (nominal mode,
every day from 6:00 hrs) to 7:30 hrs, you have to write a value of 30730
(instead of the current 30600) in register 42042.
Read and write calendar programme of switching commands via
Modbus
The 20 holding registers from 42500 to 42519 contain the 20 possible
switching commands for the calendar switching programme. For the contents
of the register, the following applies:
Command
Date
Numerical
value
(decimal)
1
3
1
1
2
13112
1 = Stand-by mode
2 = Reduced mode
3 = Normal mode
Important notes on the weekly and calendar switching programs:
All the registers for unused switching commands should contain the
value 0.
The switching commands should be entered in the chronological order of
time/date. The first command of a day/year should, therefore, be under
'Command1'.
Examples
Summary of Contents for EQJW145
Page 1: ...EQJW145 Heating controller Operating manual 7010015003 A R ...
Page 8: ...EQJW145 Heating controller Symbols used in this manual 8 7010015003 A Fr Sauter AG ...
Page 10: ...EQJW145 Heating controller General information 10 7010015003 A Fr Sauter AG ...
Page 46: ...EQJW145 Heating controller Commissioning 46 7010015003 A Fr Sauter AG ...
Page 78: ...EQJW145 Heating controller Communication functions 78 7010015003 A Fr Sauter AG ...
Page 82: ...EQJW145 Heating controller Faults 82 7010015003 A Fr Sauter AG ...
Page 90: ...EQJW145 Heating controller Economy tips 90 7010015003 A Fr Sauter AG ...
Page 94: ...EQJW145 Heating controller Dimension drawing 94 7010015003 A Fr Sauter AG ...
Page 100: ...EQJW145 Heating controller Technical data 100 7010015003 A Fr Sauter AG ...