EQJW145: Heating controller
Technical data
7010015003 A
95
© Fr. Sauter AG
14
Technical data
14.1
Overview of technical data
Power supply:
230 V
Power supply tolerance:
±
15 %, 50…60 Hz
Power consumption:
approx. 2 VA
Type of protection:
IP40 (when fitted in panels) (EN 60529)
Protection class:
II (EN 60730-1)
Permitted ambient temperature:
0…+50°C
Permitted storage temperature:
–25°C…+65°C
Permitted ambient humidity:
5…95 % rH (no condensation)
Conformity
EMC immunity
EN 12098 and CE
EN 61000-6-1, 2
EMC irradiation
EN 61000-6-3, 4
Safety
EN 60730-1
Weight with base
approx. 0.4 kg
Dimensions with base (W
×
H
×
D)
146 x 98 x 58
Time-switch:
Running capacity
Accuracy
Switching period for weekly
programme
Number of switching commands,
weekly programme
Switching period for calendar
programme
Number of switching commands,
calendar programme
Min. 24 hours, after supply was connected
for min. 4 hours. parameters, switching
commands are stored permanently
Better than 1sec/day
10 min
6 / day or 42 / week
1 day
20
Inputs:
5 temperature sensors
1 temperature sensor or remote
control unit
1 binary input/ pulse input
Outputs:
relay output for pumps/pilot timer
6 relays
normally open contact, 230V/2A/cos > 0.5
Summary of Contents for EQJW145
Page 1: ...EQJW145 Heating controller Operating manual 7010015003 A R ...
Page 8: ...EQJW145 Heating controller Symbols used in this manual 8 7010015003 A Fr Sauter AG ...
Page 10: ...EQJW145 Heating controller General information 10 7010015003 A Fr Sauter AG ...
Page 46: ...EQJW145 Heating controller Commissioning 46 7010015003 A Fr Sauter AG ...
Page 78: ...EQJW145 Heating controller Communication functions 78 7010015003 A Fr Sauter AG ...
Page 82: ...EQJW145 Heating controller Faults 82 7010015003 A Fr Sauter AG ...
Page 90: ...EQJW145 Heating controller Economy tips 90 7010015003 A Fr Sauter AG ...
Page 94: ...EQJW145 Heating controller Dimension drawing 94 7010015003 A Fr Sauter AG ...
Page 100: ...EQJW145 Heating controller Technical data 100 7010015003 A Fr Sauter AG ...