EQJW145: Heating controller
Commissioning
38
7010015003 A
© Fr. Sauter AG
If ready-for-laying heating is activated, the current phase appears:
1 = Initialisation
2 = Rising-temperature phase
3 = Temperature-maintenance phase,
4 = Falling-temperature phase
Once the floor drying has been successfully completed, the numerical value
of 9 appears. If the floor drying function was disrupted (due to a sensor
failure or a long-lasting high control offset etc.), value 8 is shown instead of 9
to signal the fault. In the case of functional heating in accordance with EN
1264 Part 4, control offset of more than 3K for more than 10 minutes is
considered to be too high. In the case of ready-for-laying heating, offset of
more than 5K for more than 30 minutes are considered to be excessive.
Values 8 and 9 can only be read. They cannot be assigned to the SERVice
parameter.
After floor drying has been completed, the EQJW 145 operates according to
the switch setting and the switching commands. Floor drying can be aborted
by setting parameter SP60 to 0. If the power supply fails, floor drying ceases.
When power is restored, the drying procedure restarts automatically.
3.4
Communication level
In the communication level, a specialist can enable and configure the
communication functions of the EQJW 145.
Incorrect parameterisation (setting) of the heating controller
It can cause major faults or damage to the installation.
The communication level must only be enabled by a specialist.
CAUTION!
Summary of Contents for EQJW145
Page 1: ...EQJW145 Heating controller Operating manual 7010015003 A R ...
Page 8: ...EQJW145 Heating controller Symbols used in this manual 8 7010015003 A Fr Sauter AG ...
Page 10: ...EQJW145 Heating controller General information 10 7010015003 A Fr Sauter AG ...
Page 46: ...EQJW145 Heating controller Commissioning 46 7010015003 A Fr Sauter AG ...
Page 78: ...EQJW145 Heating controller Communication functions 78 7010015003 A Fr Sauter AG ...
Page 82: ...EQJW145 Heating controller Faults 82 7010015003 A Fr Sauter AG ...
Page 90: ...EQJW145 Heating controller Economy tips 90 7010015003 A Fr Sauter AG ...
Page 94: ...EQJW145 Heating controller Dimension drawing 94 7010015003 A Fr Sauter AG ...
Page 100: ...EQJW145 Heating controller Technical data 100 7010015003 A Fr Sauter AG ...