EQJW145: Heating controller
Commissioning
24
7010015003 A
© Fr. Sauter AG
Parameter
Description
Range
Step value
SP49
0
Configurable output
0 = no function
1 = pilot timer function
2 = 2nd tank charge pump (MOD1, 2 only)
3 = forced control of heating medium pump at low
speed in reduced and back-up mode
4 = collective fault alarm
5 = circulating pump
0…5
1
SP50
0
Pump anti-jamming facility
0 = not enabled. 1 = enabled
0…1
1
SP51
25.10
Summer/winter time changeover
01.01 ...
31.12
SP52
25.03
Winter/summer time changeover
SP51 = SP52 means no summer/winter time
changeover
01.01 ...
31.12
SP53
0
Optimisation
0 = not enabled. 1 = enabled
0…1
1
SP60
0
Floor drying
0 = not enabled
7d = functional heating
25°C = ready-for-laying heating
8 = malfunction
9 = successfully completed
0.7d.25°C.8.9 0.7d.25°C.8
.9
Tab. 2: SERVice parameter
Summary of Contents for EQJW145
Page 1: ...EQJW145 Heating controller Operating manual 7010015003 A R ...
Page 8: ...EQJW145 Heating controller Symbols used in this manual 8 7010015003 A Fr Sauter AG ...
Page 10: ...EQJW145 Heating controller General information 10 7010015003 A Fr Sauter AG ...
Page 46: ...EQJW145 Heating controller Commissioning 46 7010015003 A Fr Sauter AG ...
Page 78: ...EQJW145 Heating controller Communication functions 78 7010015003 A Fr Sauter AG ...
Page 82: ...EQJW145 Heating controller Faults 82 7010015003 A Fr Sauter AG ...
Page 90: ...EQJW145 Heating controller Economy tips 90 7010015003 A Fr Sauter AG ...
Page 94: ...EQJW145 Heating controller Dimension drawing 94 7010015003 A Fr Sauter AG ...
Page 100: ...EQJW145 Heating controller Technical data 100 7010015003 A Fr Sauter AG ...