15
EEV-KIT Installation
1) Open the EEV-KIT cover by unscrewing 4 screws on the side of the box.
2) Drill 4 holes on the correct position of the wall and fix the EEV-KIT securely.
(Refer to the dimension of figure below.)
3) Remove the holder by unscrewing 1 screw at the plate.
4) Remove upper and lower insulations before brazing.
(Clamp doesn’t need to be loosened.)
5) Braze the pipe as indicated in figure below.
(Ensure that IN/OUT pipes are correctly connected.)
6) When the pipe become cool enough, after brazing, put the insulations back into the place.
7) Put the EEV coil into the EEV body and turn it to be fastened.
(Refer to the figure below for wiring)
8) Attach the upper insulation to the lower insulation with peeling protective layer of upper
insulation.
9) Fatsen the holder with 1 screw and close the EEV-KIT cover with 4 screws.
INSTALLATION
(Continued)
A : High pressure pipe from
outdoor unit (IN) Diameter :
Ø
9.52mm
B : High pressure pipe to AHU
heat exchanger (OUT) Diameter :
Ø
9.52mm
(Refrigerant flow under cooling mode)
1
2
• Make sure that EEV-KIT should be installed within 5m from the heat exchanger and Control-KIT.
(Supplied wire in the Accessory box is 10m.)
• Make sure that filter and valve body should be kept under 120˚C with wet cloth.
• Make sure that pipes are fully insulated. If there is any uninsulated part, it may cause condensation dripping.
• EEV-KIT should be installed in the vertical direction within the range of ± 15˚.
If it is tilted over than 15˚, it can badly affect normal operation of EEV.
30°
Vertical
Vertical
30°
Datum
plane
A
B
245mm
146mm