23
AHU-KIT heat exchanger EVA OUT sensor detachment error
Outdoor unit display
↔
xxx (xxx : Address of an indoor unit with an error)
Explanation
Refer to below explanation.
Reason
Indoor heat exchanger OUT sensor detachment.
1) Self check
• Check for AHU-KIT heat exchanger OUT sensor. Make sure it is in the correct location.
1) Explanation
• When testing run in Cool mode (Please, press the button for the test run inside the outdoor unit)
Tcond, out-Tair, out > 3˚C
OK
Tair, in-Teva, in > 4˚C
OK
Tair, in-Teva, out > 4˚C
NO
Compressor,Indoor unit in operation.
Thermo ON
OK
Error message
Indoor heat exchanger OUT sensor
detachment error
• Wired remote controller will show the same error shown in the outdoor unit.
Sensor Error
AHU-KIT heat exchanger IN sensor detachment error
Outdoor unit display
↔
xxx (xxx : Address of an indoor unit with an error)
Explanation
Refer to below explanation.
Reason
Indoor heat exchanger IN sensor detachment.
2) Self check
• Check for IN sensor of AHU-KIT heat exchanger. Make sure it is in the correct location.
1) Explanation
• When testing run in Cool mode (Please, press the button for the test run inside the outdoor unit)
Tcond, out-Tair, out > 3˚C
OK
Tair, in-Teva, in > 4˚C
NO
Tair, in-Teva, out > 4˚C
OK
Compressor,Indoor unit in operation. Thermo ON
OK
Error message
Indoor heat exchanger IN sensor
detachment error
TROUBLESHOOTING
(Continued)
Note
• When conditions shown in above table occurs, it is classified as
↔
xxx
• When conditions shown in above table occurs, it is classified as
↔
xxx
MXD-A16K1X025A_E_31836-1.indd 23
2010-03-12 ソタネト 12:43:07