22
Initial Check-up
1) Check the connection status between Indoor unit and the AHU-KIT.
• Make sure you have followed instructions and wiring diagram shown in the installation manual.
• Make sure AHU-KIT PBA is installed in a place where there are no influence from outdoor humidity,
dust and temperature.
2) Ensure that power voltage is AC 187V~AC 253V.
3) Check each of the accessories and make sure they are in good condition.
• CN32 : DC 11~13V (both ends)
• IC02 G/O : DC 4.5~5.5V (both ends)
• TRANS Output : AC 16~18V
Outdoor unit display
Explanation
Internal communication error between EEPROM and MICOM
Reason
Require to change PBA due to Bad EEPROM
EEPROM Error
• Wired remote controller will show the same error shown in the outdoor unit.
TROUBLESHOOTING
Note
MXD-A16K1X025A_E_31836-1.indd 22
2010-03-12 ソタネト 12:43:06