19
Setting the Address
1 2 3 4 1 2 3 4 1 2 3 4
K1K2K3K4
K5K6K7K8
K9K10K11K12
CN41:EVA IN & ROOM
sensor socket
CN42:EVA OUT
sensor socket
10HP(MXD-A22K200X): Connect EEV to CN62/CN60
(Match the color of EEV connector and the socket)
5HP(MXD-A22K100X) : Connect EEV to CN62 Only
(Do not connect CN60)
DIP Switch for option
MAIN
RMC
CN41
CN42
CN62
CN60
• After the installation, you have to set up the address.
Use MAIN and RMC switch to set the AHU-KIT address.
•
2.5HP(MXD-A16K1X025A)/5HP(MXD-A22K1X050A) : Connect EEV to CN62 Only (Do not connect CN60)
7.5HP(MXD-A22K2X075A)/10HP(MXD-A22K2X100A): Connect EEV to CN62/CN60
(Match the color of EEV connector and the socket)
Use the rotary switch to set up the address for each of the AHU-KIT.
Default setting is 0.
FUNCTION SETTING
• Try not to touch other parts of the PBA with your hands when setting the address.
Part may get damaged due to static electricity.