12
INSTALLATION
(Continued)
Operational Voltage range against Setting temperature
Simple BMS
Voltage Range
Set Temperature
Heat
Cool
10.0V ~ 9.6V
30˚C
30˚C
9.6V ~ 9.2V
30˚C
30˚C
9.2V ~ 8.8V
30˚C
30˚C
8.8V ~ 8.4V
30˚C
30˚C
8.4V ~ 8.0V
30˚C
30˚C
8.0V ~ 7.6V
30˚C
30˚C
7.6V ~ 7.2V
29˚C
29˚C
7.2V ~ 6.8V
28˚C
28˚C
6.8V ~ 6.4V
27˚C
27˚C
6.4V ~ 6.0V
26˚C
26˚C
6.0V ~ 5.6V
25˚C
25˚C
5.6V ~ 5.2V
24˚C
24˚C
5.2V ~ 4.8V
23˚C
23˚C
4.8V ~ 4.4V
22˚C
22˚C
4.4V ~ 4.0V
21˚C
21˚C
4.0V ~ 3.6V
20˚C
20˚C
3.6V ~ 3.2V
19˚C
19˚C
3.2V ~ 2.8V
18˚C
18˚C
2.8V ~ 2.4V
18˚C
18˚C
2.4V ~ 2.0V
18˚C
18˚C
2.0V ~ 1.6V
18˚C
18˚C
1.6V ~ 1.2V
18˚C
18˚C
1.2V ~ 0.8V
18˚C
18˚C
0.8V ~ 0.4V
18˚C
18˚C
0.4V ~ 0.0V
18˚C
18˚C
Setting the temperature
• Keep the power supply of Simple BMS in 10 V ± 0.2 V.
• If the Simple BMS uses variable resistor(VR), make the electric resistance of VR under 1
㏀
.
• Simple BMS which uses variable resistor(VR) need to be connected to the AHU-KIT with 1:1 link.
• Use the Simple BMS which outputs voltage so that one Simple BMS controls several AHU-KIT at the same time.
AHU-KIT
AHU-KIT
BMS_Temp.Set
DC10V
V1
47K-F
47K-F
VCC_CIRCLE
47K-F
47K-F
VCC_CIRCLE
R1
1K
2
1
2
1
+
-
AHU-KIT
AHU-KIT
DC0V ~
DC10V
V1
47K-F
47K-F
47K-F
47K-F
VCC_CIRCLE
VCC_CIRCLE
BMS_Temp.Set
2
1
2
1
AHU-KIT
AHU-KIT
BMS_Temp.Set
DC10V
+
-
+
-
+
-
V1
47K-F
47K-F
47K-F
47K-F
VCC_CIRCLE
VCC_CIRCLE
R1
1K
R2
1K
DC10V
V2
2
1
BMS_Temp.Set
2
1
2
1
Available
Not Available
• Make sure that Simple BMS is connected to
DC power supply before installing.
Never connect Simple BMS to AC power supply .
MXD-A16K1X025A_E_31836-1.indd 12