21
Setting Up Function Switch
Switch No.
Function
ON (Default)
OFF
SW05
K1 External Thermistor
Disable
Enable
K2 Centralized control
Disable
Enable
K3 Setting up Capacity 1
K3 and K4 Set up the capacity.
Refer to the table below.
K4 Setting up Capacity 2
SW06
K5
Room temperature
compansation for Heating
+2
℃
+5
℃
K6 Fan feedback
Disable
Enable
K7 Prevent cold wind
Enable
Disable
K8 Defrost Bypass Valve
Disable
Enable
SW07
K9 Stop Unit EEV Indoor
80 step, fixed
0 or 80 step
K10 Setting up Master Imdoor
Slave
Master
K11 External control
Disable
Enable
K12
Setting up External control
output signals
Thermo ON/OFF
Operating ON/OFF
K
1K2K3K4
K5K6K7K8
K9K10K11K12
Factory default
SW05(K3 , K4) switches are all set in ON position as factory default.
In case of operating other capacity, set the switches following the table.
Ex.)
FUNCTION SETTING
(Continued)
Note
2.5HP
5HP
7.5HP
10HP
K1K2K3K4
K
1K2K3K4
K1K2K3K4
K1K2K3K4
K1K2K3K4
Setting up capacity
K3
K4
Capacity
ON
OFF
2.5HP
ON
ON
5.0HP
OFF
ON
7.5HP
OFF
OFF
10HP