Troubleshooting
4-62
Samsung Electronics
1. Low pressure sensor Open / Short error determination method
1) Identifies from when power is supplied or 2 minutes after RESET, and only when set is stopped.
2) An Open / Short error will occur if the input voltage standard range of 0.5V~4.95V is exceeded.
2. How to check
غ
AM038/048/055KXWD
✳✳
Outdoor unit display
Indoorunit display
Duct, Cassette (1/2 Way),Console, Celing
Cassette (4/Mini4 Way)
Wall-mounted (NeoForte)
Operation
Defrost
Timer
Fan
Filter/MPI Operation Defrost
Timer
Filter
18
℃
21
℃
Turbo
24
℃
27
℃
◑
×
×
◑
×
◑
×
◑
×
◑
×
×
◑
×
※ ● :
ON
◑ :
Flash
× :
OFF
Judgment Method
∙ Refer to the how to check below..
Cause of problem
∙ Disconnection or breakdown of relevant sensor.
Low pressure sensor error (Open / Short)
(cont.)
Replace low pressure sensor
Restart after connecting the connector to the PCB
No
Yes
Did the high pressure sensor connector breakaway
from the PCB?
Charge the refrigerant after vacuum
No
Yes
Is there refrigerant inside the set?
(Please check by connecting the manifold gauge to
the service valve)
Replace PCB
No
Yes
Out of the PCB low pressure sensor terminals,
is there voltage between pins (3 and 4) 5V?
The
ف
mark is the 1st pin on the PCB.
Summary of Contents for AM072/096/120/144FXVAFH
Page 220: ...5 6 Samsung Electronics 5 2 ASS YPCBMAIN HUB AC 1 2 3 4 5 6 7 8 9 10 11 12...
Page 224: ...5 10 Samsung Electronics 4 2 3 5 8 9 7 1 6 5 3 ASSY PCB INVERTER...
Page 226: ...5 12 Samsung Electronics ASS Y PCB INVERTER cont 4 8 10 9 7 6 11 12 13 1 2 3 5...
Page 230: ...5 16 Samsung Electronics 5 5 ASS YPCBFAN Model 1 FANchassis 1 5 2 6 3 4...
Page 232: ...5 18 Samsung Electronics ASS YPCBFAN cont Model 2 FAN chassis 1 7 2 8 3 4 5 9 6...
Page 238: ......
Page 239: ......
Page 240: ......
Page 241: ......
Page 242: ......
Page 243: ......
Page 244: ......
Page 245: ......
Page 262: ...7 16 Samsung Electronics 7 20 AM038KXWD66 7 21 AM048 055KXWD66...