3-68
Samsung Electronics
3) Checking of oil circulating system
ᐭ
Oil separator capillary tube or filter of block
- If filter or capillary tube of oil separator lower column is blocked by alien substance etc.., can become cause of compressor break-
down because oil is not collected.
- Can doubt that is blocked if oil separator capillary tube temperature is low after refrigerant outlet temperature of compressor, in
driving, rises.
(
ఐ
Compressor 2 individual occasion oil separator capillary tubes each other cross.)
- Confirm that is blocked in stationary state through nitrogen pressurization availability.
ᐮ
Breakdown of Accum Oil Return Valve (ARV)
- Damage can become cause of compressor breakdown because oil is not collected if filter of valve front/piping etc.. is blocked
with ARV is closed.
- Power connector of ARV confirms that was linked right.
- Extract connector in vacuum mode or confirm whether when insert, action sound of valve happens.
ᐯ
When CCH is badness, can become cause of compressor breakdown by oil foaming.
͞
AM072/096/120/192HXWA
✳✳
Summary of Contents for AM072/096/120/144FXVAFH
Page 220: ...5 6 Samsung Electronics 5 2 ASS YPCBMAIN HUB AC 1 2 3 4 5 6 7 8 9 10 11 12...
Page 224: ...5 10 Samsung Electronics 4 2 3 5 8 9 7 1 6 5 3 ASSY PCB INVERTER...
Page 226: ...5 12 Samsung Electronics ASS Y PCB INVERTER cont 4 8 10 9 7 6 11 12 13 1 2 3 5...
Page 230: ...5 16 Samsung Electronics 5 5 ASS YPCBFAN Model 1 FANchassis 1 5 2 6 3 4...
Page 232: ...5 18 Samsung Electronics ASS YPCBFAN cont Model 2 FAN chassis 1 7 2 8 3 4 5 9 6...
Page 238: ......
Page 239: ......
Page 240: ......
Page 241: ......
Page 242: ......
Page 243: ......
Page 244: ......
Page 245: ......
Page 262: ...7 16 Samsung Electronics 7 20 AM038KXWD66 7 21 AM048 055KXWD66...