Test Operation
Samsung Electronics
9-7
4) Pressure sensor (Independent installation)
Ŷ
Inspection item : High/Low Pressure sensor of the independent installed Outdoor Unit.
Ŷ
Error code: None (The resulting report "Undetermined")
Ŷ
Determine the status of the Pressure sensor of the independent installed Outdoor Unit before the compressor start.
Ŷ
If the judgment of Outdoor Unit Pressure sensor is "Undetermined" : Checking in accordance with the following order.
[Caution]
- If the Outdoor Unit with a history of operation (Auto Trial Operation inclusion) : Maintain the vacuum mode for more than 5 minutes.
Yes
Confirmation and Measures
No
Is Pressure sensor connector properly connect?
Yes
Replace Hub PCB
No
Is voltage 5
V
between
3, 4 pin of PCB Pressure sensor terminal?
Yes
Replace PCB
No
Is deviation of outdoor
unit as following?"High pressure Max
/Min deviation : less than 2"
Off the vacuum mode of Outdoor Unit
Check the pressure sensor breakdown
Complete
V
acuum mode of Outdoor Unit
※
Check the Pressure sensor breakdown after the saturation pressure
of the outdoor temperature or connect the manifold gauge to check the pressure
.
Summary of Contents for AM072/096/120/144FXVAFH
Page 220: ...5 6 Samsung Electronics 5 2 ASS YPCBMAIN HUB AC 1 2 3 4 5 6 7 8 9 10 11 12...
Page 224: ...5 10 Samsung Electronics 4 2 3 5 8 9 7 1 6 5 3 ASSY PCB INVERTER...
Page 226: ...5 12 Samsung Electronics ASS Y PCB INVERTER cont 4 8 10 9 7 6 11 12 13 1 2 3 5...
Page 230: ...5 16 Samsung Electronics 5 5 ASS YPCBFAN Model 1 FANchassis 1 5 2 6 3 4...
Page 232: ...5 18 Samsung Electronics ASS YPCBFAN cont Model 2 FAN chassis 1 7 2 8 3 4 5 9 6...
Page 238: ......
Page 239: ......
Page 240: ......
Page 241: ......
Page 242: ......
Page 243: ......
Page 244: ......
Page 245: ......
Page 262: ...7 16 Samsung Electronics 7 20 AM038KXWD66 7 21 AM048 055KXWD66...