Troubleshooting
Samsung Electronics
4-79
4-4-34-phase Input Wiring error
Outdoor unit display
Indoorunit display
Judgment Method
. When turn on the power and check the status of the power from the inverter.
If the phase does not connect the power(no phase) : E425 or E466 (E366) is displayed
(Air conditioner to maintain the normal state.)
However) N-phase must be properly connected.
Cause of problem
∙ Check the input wiring
∙ EMI Fuse short
Duct, Cassette (1/2 Way),Console, Celing
Cassette (4/Mini4 Way)
Wall-mounted (NeoForte)
Operation
Defrost
Timer
Fan
Filter/MPI Operation Defrost
Timer
Filter
Operation
Timer
Turbo
×
×
◑
◑
◑
×
◑
◑
◑
●
◑
◑
※ ● :
ON
◑ :
Flash
× :
OFF
1. How to check
Replace the MAIN PCB.
Connection and then restart it
Power BOX Terminal : Check the phase-to-phase
connection 380V of the R, S, T and then restart.
(N-phase must be properly connected.)
No
No
Yes
Yes
Did the Reactor
Connection Terminal is connected
properly?
Did the Main
Terminal Block and Power R, S, T, N is
connected properly?
Low voltage error during this initial charge :
Replace Fuse, if the rectifier diode of the
inverter PCB is normal.
No
No
Did the EMI PCB Fuse is short?
Connection and then restart it
Yes
Yes
Is EMI PCB CN21
connector and Inverter PCB accurately
connected?
Power Off
Summary of Contents for AM072/096/120/144FXVAFH
Page 220: ...5 6 Samsung Electronics 5 2 ASS YPCBMAIN HUB AC 1 2 3 4 5 6 7 8 9 10 11 12...
Page 224: ...5 10 Samsung Electronics 4 2 3 5 8 9 7 1 6 5 3 ASSY PCB INVERTER...
Page 226: ...5 12 Samsung Electronics ASS Y PCB INVERTER cont 4 8 10 9 7 6 11 12 13 1 2 3 5...
Page 230: ...5 16 Samsung Electronics 5 5 ASS YPCBFAN Model 1 FANchassis 1 5 2 6 3 4...
Page 232: ...5 18 Samsung Electronics ASS YPCBFAN cont Model 2 FAN chassis 1 7 2 8 3 4 5 9 6...
Page 238: ......
Page 239: ......
Page 240: ......
Page 241: ......
Page 242: ......
Page 243: ......
Page 244: ......
Page 245: ......
Page 262: ...7 16 Samsung Electronics 7 20 AM038KXWD66 7 21 AM048 055KXWD66...