Troubleshooting
Samsung Electronics
4-17
غ
Diagnosis and Adjustment (Error Code)
ـ
Error code related to the Communications / Settings / HW
(cont.)
Error mode
Cause
E-462
Compressor stop due to full current control or error due to low current on CT2
E-464
Error due to over-current of inverter compressor 1
E-465
V-limit error of inverter compressor 1
E-466
Error due to over voltage /low voltage of inveter PBA1
E-467
Error due to unconnected wire of compressor 1
E-468
Output current sensor error of inverter PBA1
E-469
DC voltage sensor error of inver PBA1
E-474
Heat sink temperature sensor error of inverter PBA1
E-478
Error due to overcurrent of Fan1
E-485
Error due to input current of inverter 1
E-486
Error due to over voltage/low voltage of Fan
E-487
Hall IC error of Fan1
E-489
V-limit error on Fan1 of compressor
E-493
Output current sensor error of Fan1
E-496
DC voltage sensor error of Fan1
E-499
Heat sink temperature sensor error of Fan1
E-500
Error due to overheat caused by contact failure on IPM of Inverter PBA1
E-503
Error due to alert the user to check if the service valve is closed
E-504
Error due to self diagnosis of compressor operation
E-505
Error due to self diagnosis of high pressure sensor
E-506
Error due to self diagnosis of low pressure sensor
E-560
Outdoor unit's option switch setting error (when iinappropriate option switch is on)
E-563
Error due to module installation of indoor unit with old version
(Micom version needs to be checked)
E-573
Error due to using single type outdoor unit in a module installation
E-702
Error due to closed EEV of indoor unit (1st detection)
E-703
Error due to opened EEV of indoor unit (1st detection)
E-901
EHS water in sensor (Short or Open)
E-902
EHS water out sensor (Short or Open)
E-904
EHS water tank sensor (Short or Open)
E-907
EHS freezing protection srror
E-908
EHS freezing protection error (EHS reoperatable)
E-909
EHS freezing protection error (EHS not reoperatable)
E-910
EHS water out sensor detached
E-911
EHS flow switch error
E-913
EHS flow switch error (6th detection)(EHS not reoperatable)
E-914
EHS thermostat detached
E-915
EHS radiating fan unoperate error
UP
Auto Trial Operation incompleted (UnPrepared)
Summary of Contents for AM072/096/120/144FXVAFH
Page 220: ...5 6 Samsung Electronics 5 2 ASS YPCBMAIN HUB AC 1 2 3 4 5 6 7 8 9 10 11 12...
Page 224: ...5 10 Samsung Electronics 4 2 3 5 8 9 7 1 6 5 3 ASSY PCB INVERTER...
Page 226: ...5 12 Samsung Electronics ASS Y PCB INVERTER cont 4 8 10 9 7 6 11 12 13 1 2 3 5...
Page 230: ...5 16 Samsung Electronics 5 5 ASS YPCBFAN Model 1 FANchassis 1 5 2 6 3 4...
Page 232: ...5 18 Samsung Electronics ASS YPCBFAN cont Model 2 FAN chassis 1 7 2 8 3 4 5 9 6...
Page 238: ......
Page 239: ......
Page 240: ......
Page 241: ......
Page 242: ......
Page 243: ......
Page 244: ......
Page 245: ......
Page 262: ...7 16 Samsung Electronics 7 20 AM038KXWD66 7 21 AM048 055KXWD66...