Troubleshooting
4-72
Samsung Electronics
4-4-31
: Comp. Down due to High Pressure Protection Control
1. How to check
Is the S-net
estimated value and theManifold
Gauge value in range?
Are the Indoor Unit
and Outdoor Unit EEV normally
operating?
Are there any blockage inside
the pipe? (filter etc.)
Check the refrigerant amount.
Are the Outdoor Fan
operating normally for the cooling
and the Indoor Fan operating normally
for the heating?
Auto Trial Operation
Open the Service Valve
Replace High Pressure sensor
Check the relevant EEV
Pipe inspection
Replace relevant component
(motor or fan)
Yes
Yes
Yes
No
Yes
Are all service valves open?
Connect S-net and Manifold Gauge.
(essential requirement)
No
No
No
Yes
No
Outdoor unit display
( Air Cooled )
Indoorunit display
Duct, Cassette (1/2 Way),Console, Celing
Cassette (4/Mini4 Way)
Wall-mounted (NeoForte)
Operation
Defrost
Timer
Fan
Filter/MPI Operation Defrost
Timer
Filter
Operation
Timer
Turbo
×
×
◑
◑
◑
×
◑
◑
◑
●
◑
◑
※ ● :
ON
◑ :
Flash
× :
OFF
Judgment Method
∙ Value of the high pressure sensor is detected at 41kg/cm² or more
Cause of problem
<Cooling Operation>
∙ Outdoor unit fan motor problem (constrained, defective)
∙ Outdoor heat exchanger is contaminated.
∙ Service valve locked/Fill refrigerant
<Heating Operation>
∙ Service valve locked/Excessive refrigerant
Summary of Contents for AM072/096/120/144FXVAFH
Page 220: ...5 6 Samsung Electronics 5 2 ASS YPCBMAIN HUB AC 1 2 3 4 5 6 7 8 9 10 11 12...
Page 224: ...5 10 Samsung Electronics 4 2 3 5 8 9 7 1 6 5 3 ASSY PCB INVERTER...
Page 226: ...5 12 Samsung Electronics ASS Y PCB INVERTER cont 4 8 10 9 7 6 11 12 13 1 2 3 5...
Page 230: ...5 16 Samsung Electronics 5 5 ASS YPCBFAN Model 1 FANchassis 1 5 2 6 3 4...
Page 232: ...5 18 Samsung Electronics ASS YPCBFAN cont Model 2 FAN chassis 1 7 2 8 3 4 5 9 6...
Page 238: ......
Page 239: ......
Page 240: ......
Page 241: ......
Page 242: ......
Page 243: ......
Page 244: ......
Page 245: ......
Page 262: ...7 16 Samsung Electronics 7 20 AM038KXWD66 7 21 AM048 055KXWD66...