8-12
Samsung Electronics
How to set the key function of the outdoor unit
(cont.)
䒲
AM072/096/120/192HXWA
66
Optional item
Input unit SEG1 SEG2 SEG3 SEG4
Function of the option
Remarks
Setting longpiping
condition
(Setting is unnecessary
if high-head condition
is set.)
Main
0
9
0
0
Disable (Factory default)
0
1
Long piping level 1
When equivalent length of
farthest indoor unit from
the outdoor unit is between
100~170 m
0
2
Long piping level 2
When equivalent length of
farthest indoor unit from the
outdoor unit is over 170 m
Energy saving
setting
Main
1
0
0
0
Disable (Factory default)
0
1
Enable
Energy saving mode triggers
when the room temperature
reaches desired temperature
while operating in heating
mode.
Disable
Main
1
1
0
0
Disable
This function is not applicable for
this model
0
1
Disable
Expand operational
temperature range for
cooling operation
Main
1
2
0
0
Disable
0
1
Enable
Channel address
Main
1
3
A
U
Automatic setting (Factory
default)
Address for classifying the
product from upper level
controller (DMS, S-NET 3, etc)
0 ~ 15
Manual setting for channel 0~15
Disable
Main
1
4
0
0
Disable
This function is not applicable for
this model
0
1
Disable
Circulation water
flow control
Individual
1
5
0
0
Disable (Factory default)
0
1
7-10 V
When variable flow control valve is
applied
0
2
5-10 V
0
3
3-10 V
Summary of Contents for AM072/096/120/144FXVAFH
Page 220: ...5 6 Samsung Electronics 5 2 ASS YPCBMAIN HUB AC 1 2 3 4 5 6 7 8 9 10 11 12...
Page 224: ...5 10 Samsung Electronics 4 2 3 5 8 9 7 1 6 5 3 ASSY PCB INVERTER...
Page 226: ...5 12 Samsung Electronics ASS Y PCB INVERTER cont 4 8 10 9 7 6 11 12 13 1 2 3 5...
Page 230: ...5 16 Samsung Electronics 5 5 ASS YPCBFAN Model 1 FANchassis 1 5 2 6 3 4...
Page 232: ...5 18 Samsung Electronics ASS YPCBFAN cont Model 2 FAN chassis 1 7 2 8 3 4 5 9 6...
Page 238: ......
Page 239: ......
Page 240: ......
Page 241: ......
Page 242: ......
Page 243: ......
Page 244: ......
Page 245: ......
Page 262: ...7 16 Samsung Electronics 7 20 AM038KXWD66 7 21 AM048 055KXWD66...