![Samsung AM072/096/120/144FXVAFH Service Manual Download Page 146](http://html1.mh-extra.com/html/samsung/am072-096-120-144fxvafh/am072-096-120-144fxvafh_service-manual_4744881146.webp)
Troubleshooting
Samsung Electronics
4-49
4-4-18 Cond Out Temperature Sensor Error (Open/Short)
∙ Disconnection or breakdown of relevant sensor.
∙ Refer to the judgment method below.
Indoorunit display
Judgment Method
Cause of problem
Outdoor unit display
1. How to check
Yes
Is the COND OUT
sensor connector (CN43) connected
to PCB?
Did the resistance
value significantly stray from the following
temperature table?
After separating the outdoor Cond Out
sensor connector from the PCB, measure the
resistance value between the two terminals.
Restart operation after replace the PCB
Restart operation after connecting
the connector to the PCB.
Replace this part as it is the defective of the
outdoor Cond Out sensor itself.
Yes
No
No
Temperature (°C)
70
60
50
40
30
20
10
0
-10
Resistance (KΩ)
2.2
3.0
4.2
5.8
8.3
12.1
18.0
27.3
43.0
Resistance value measure part
COND
COND
Duct, Cassette (1/2 Way),Console, Celing
Cassette (4/Mini4 Way)
Wall-mounted (NeoForte)
Operation
Defrost
Timer
Fan
Filter/MPI Operation Defrost
Timer
Filter
Operation
Timer
Turbo
24
℃
27
℃
◑
×
×
◑
×
◑
×
◑
×
◑
×
×
◑
×
※ ● : ON ◑ : Flash × : OFF
Summary of Contents for AM072/096/120/144FXVAFH
Page 220: ...5 6 Samsung Electronics 5 2 ASS YPCBMAIN HUB AC 1 2 3 4 5 6 7 8 9 10 11 12...
Page 224: ...5 10 Samsung Electronics 4 2 3 5 8 9 7 1 6 5 3 ASSY PCB INVERTER...
Page 226: ...5 12 Samsung Electronics ASS Y PCB INVERTER cont 4 8 10 9 7 6 11 12 13 1 2 3 5...
Page 230: ...5 16 Samsung Electronics 5 5 ASS YPCBFAN Model 1 FANchassis 1 5 2 6 3 4...
Page 232: ...5 18 Samsung Electronics ASS YPCBFAN cont Model 2 FAN chassis 1 7 2 8 3 4 5 9 6...
Page 238: ......
Page 239: ......
Page 240: ......
Page 241: ......
Page 242: ......
Page 243: ......
Page 244: ......
Page 245: ......
Page 262: ...7 16 Samsung Electronics 7 20 AM038KXWD66 7 21 AM048 055KXWD66...