30
Installation Procedure
Ins
tallation Pr
oc
edur
e
English
Option
SEG13
SEG14
SEG15
SEG16
SEG17
SEG18
Explanation
PAGE
Use of external control
Setting the output of external control /
External heater On/Off signal
S-Plasma ion
Buzzer control
Hours of filter usage
Indication
and Details
Indication
Details Indication
Details Indication
Details
Indication
Details
Indication
Details
Indication
Details
Setting the
output of
external
control
External heater
On/Off signal
2
0
Disuse
0
Thermo on
-
0
Disuse
0
Use buzzer
2
1000 Hour
1
ON/OFF
control
1
Operation on
-
1
Use
1
Disuse buzzer
6
2000 Hour
2
OFF
control
2
-
Use (*4)
3
Window
ON/OFF
control
3
-
Use (*4)
Option
SEG19
SEG20
SEG21
SEG22
SEG23
SEG24
Explanation
PAGE
Individual control of a
remote control
Heating setting compensation / Removing
condensated water in heating mode
EEV Step of stopped unit during oil
return/defrost mode
-
Indication
and Details
Indication Details Indication
Details Indication
Details
Indication
Details
Heating
Setting
Compensation
Removing
Condensated
Water in
Heating Mode
3
0 or 1
channel 1 0
Default (*5)
Disuse
0
Default value
2
channel 2
1
2 °C
Disuse
1
Oil return or Noise
decreasing in defrost mode
3
channel 3
2
5 °C
Disuse
4
channel 4
3
Default (*5) Use (*6)
4
2 °C
Use (*6)
5
5 °C
Use (*6)
(*)
Advanced function: Controlling cooling/heating current or power saving with motion detect.
(*1)
Minimizing fan operation when thermostat is off
– Fan operates for 20 seconds at an interval of 5 minutes in
Heat
mode.
(*2)
1: Fan is turned on continually when the hot water heater is turned on, 3: Fan is turned off when the hot water
heater is turned on with cooling only indoor unit
Cooling only indoor unit: To use this option,install the
Mode Select switch
(MCM-C200) on the outdoor unit and fix
it as
Cool
mode.
(*3)
It is only for wall-mounted indoor unit with EEV Integrated. If any design condition meets either of the following
below, please set SEG11 to “7”.
a
The total number of wall-mounted indoor units with EEV Integrated in one (modular) system is more than 20.
b
The total number of wall-mounted indoor units with EEV Integrated in one (modular) system is more than “the
total of one(modular) system’s capacity(kW) / 2” (“the total of one(modular) system’s capacity(BTU/h) / 6800”).
ex) Outdoor capacity 28kW
→
28 /2 = 14. The total number of wall-mounted indoor units with EEV Integrated
in one (modular) system is more than 14.