10
Installation Procedure
Ins
tallation Pr
oc
edur
e
English
AE090MNMPEH
(Unit: mm)
700
604
30-ø3.2 hole
(Air around)
1100(11x100)
1167 (Air outlet duct flange)
1200
1250 (Suspension position)
700
1200
500
1300
Suction side
Discharge side
220
180(2x90)
250
213
125
323
06
07
05
01
02
04
03
185
158
28
Inspection hole
No.
Name
Description
01
Liquid pipe connection
ø9.52(3/8")
02
Gas pipe connection
ø15.88(5/8")
03
Drain pipe connection
OD25 ID20(without drain pump)
04
Power supply connection
05
Air discharge flange
06
Air filter
07
Hook
M8~M10
Summary of Contents for AE071MNMPEH