background image

14

Installation Procedure

Ins
tallation Pr

oc

edur

e

English

Check if you flared the pipe correctly. There are some 
examples of incorrectly flared pipes below. 

Inclined

Damaged

Surface

Cracked

Uneven

Thickness

Align the pipes and tighten the flare nuts first manually 
and then with a torque wrench, applying the following 
torque.

R 0.4~0.8

90°±2°

45

°±2°

L

D

Outer 

diameter (D, 

mm)

Connection Torque

Flare dimension  

(L, mm)

kgf•cm

N•m

6.35

140~180

14~18

8.70~9.10

9.52

350~430

34~42

12.80~13.20

2.70

500~620

49~61

16.20~16.60

15.88

690~830

68~82

19.30~19.70

  CAUTION

• 

In case of needing brazing, you must work with 
nitrogen gas blowing.

Step 7  Connecting the assembly 
pipes to the refrigerant pipes

There are two refrigerant pipes of different diameters :

• 

A smaller one for the liquid refrigerant

• 

A larger one for the gas refrigerant

• 

The inside of copper pipe must be clean & has no dust

Remove the pinch pipe on the pipes and connect the 
assembly pipes to each pipe, tightening the nuts, first 
manually and then with a torque wrench, a spanner 
applying the following torque.

Torque wrench

Flare nut

Union

Spanner

Refrigerant oil

Outer diameter (D)

Torque (N•m)

Ø6.35 mm

14 ~ 18

Ø9.52 mm

34 ~ 42

Ø12.70 mm

49 ~ 61

Ø15.88 mm

68 ~ 82

Ø19.05 mm

100 ~ 120

  NOTE

• 

  If the pipes must be shortened refer to page 

13

Step 6  Cutting or flaring the pipes

Be sure to use insulator which is thick enough to cover 
the refrigerant tube to protect the condensate water 
on the outside of pipe falling onto the floor and the 
efficiency of the unit will be better.

Cut off any excess foam insulation.

Be sure that there must be no crack or wave on the 
bended area.

It would be necessary to double the insulation 
thickness(10mm or more) to prevent condensation even 
on the insulator when if the installed area is warm and 
humid.

Do not use joints or extensions for the pipes that 
connect the indoor and outdoor unit. The only permitted 
connections are those for which the units are designed.

Summary of Contents for AE071MNMPEH

Page 1: ...conditioner Installation manual AE MNLDEH AE MNMPEH Thank you for purchasing this Samsung air conditioner Before operating this unit please read this manual carefully and retain it for future referen...

Page 2: ...refrigerant pipes Step 8 Performing the gas leak test Step 9 Insulating the refrigerant pipes Step 10 Installing the drain hose and drain pipe Step 11 Performing the drainage test Step 12 Connecting t...

Page 3: ...nges or the improper connection of electric and requirements set forth in the Operating limits table included in the manual shall immediately invalidate the warranty The air conditioner should be used...

Page 4: ...other elevation system will NOT be considered part of the warranty and will be charged to the end customer Power supply line fuse or circuit breaker WARNING Always make sure that the power supply is c...

Page 5: ...d Resin parts flame and the accessories may drop or water may leak The capacity of the heat exchanger may reduce or the air conditioner may be out of order The place where corrosive gas such as sulphu...

Page 6: ...nstalled at the end of the installation It is always essential to check the efficiency of the drainage system Space requirements for installation Construction Standard for Inspection Hole 1 In case th...

Page 7: ...ion 18 3 2 hole Air around 660 Air outlet duct flange 28 28 600 600 6x100 700 5 05 06 07 Suction side 333 199 Discharge side 182 246 151 6 18 100 02 01 03 04 No Name Description 01 Liquid pipe connect...

Page 8: ...flange 900 22 3 2 Hole 28 28 All around Discharge side Suction side 199 151 6 100 182 246 18 OD32 30 5 115 5 145 5 333 No Name Description 01 Liquid pipe connection 6 35 1 4 02 Gas pipe connection 12...

Page 9: ...ension position 604 Suspension position 700 500 850 950 185 158 28 220 180 2x90 250 213 125 323 06 07 05 01 02 04 03 No Name Description 01 Liquid pipe connection 6 35 1 4 02 Gas pipe connection 035 9...

Page 10: ...pension position 700 1200 500 1300 Suction side Discharge side 220 180 2x90 250 213 125 323 06 07 05 01 02 04 03 185 158 28 Inspection hole No Name Description 01 Liquid pipe connection 9 52 3 8 02 Ga...

Page 11: ...n duct and discharge duct Unit mm NOTE Insulate the end of the pipe and some curved area by using separate insulator Insulate the discharge and suction part at the same time when you insulate connecti...

Page 12: ...between two nuts 1 2 2 CAUTION Piping must be laid and connected inside the ceiling when suspending the unit If the ceiling is already constructed lay the piping into position for connection to the u...

Page 13: ...0700kPa Copper pipe for hydro sanitary applications is completely unsuitable For sizing and limits height difference line length max bends refrigerant charge etc see the outdoor unit installation manu...

Page 14: ...1 Remove the pinch pipe on the pipes and connect the assembly pipes to each pipe tightening the nuts first manually and then with a torque wrench a spanner applying the following torque Torque wrench...

Page 15: ...g the refrigerant gas pressurize the whole system with nitrogen using a cylinder with a pressure reducer at a pressure above 4 MPa in order to immediately detect leaks on the refrigerant fittings Made...

Page 16: ...side and liquid side pipe noting the insulation thickness that must differ according to the pipe size Standard Less than an indoor temperature of 30 C with humidity at 85 If installing in a high humid...

Page 17: ...0mm Step 10 Installing the drain hose and drain pipe 1 Push the supplied drain hose as far as possible over the drain socket 2 Tighten the metal clamp as shown in the picture 3 Wrap the supplied large...

Page 18: ...e installed upward position it may cause water flow back to the indoor unit 1 1 5m 20mm or more 200mm or more Hanger Within 300 550mm Air vent 300mm or less Flexible hose Horizontal drainpipe more tha...

Page 19: ...N among the units within maximum length and communication cable F1 F2 each 5 Connect F3 F4 for communication wires when installing the wired remote control N L N L N L N L ELCB MCCB ELB V1 V2 Outdoor...

Page 20: ...screw mm B C d1 E F L d2 t Standard dimension mm Allowance mm Standard dimension mm Allowance mm Standard dimension mm Allowance mm Min Min Max Standard dimension mm Allowance mm Min 1 5 4 6 6 0 2 3...

Page 21: ...ower cable in accordance with relevant local and national regulations Wire size must comply with local and national code For the power cable use the grade of H07RN F or H05RN F materials You should co...

Page 22: ...driver with a small head will strip the head and make proper tightening impossible Over tightening the terminal screws may break them See the table below for tightening torque for the terminal screws...

Page 23: ...th the insulation tape twice or more and position your contraction tube in the middle of the insulation tape Three or more layers of insulation are required Method 1 Method 2 Insulation tape Insulatio...

Page 24: ...option setting mode while pressing High Temp button and Low Temp button 3 Check if you have entered the option setting status 4 After entering the option setting status select the option CAUTION Optio...

Page 25: ...ed to Dry mode in the ON status 5 Setting SEG6 SEG8 option a Press Low Fan button to enter SEG6 value b Press High Fan button to enter SEG8 value Each time you press the button will be selected in rot...

Page 26: ...button to enter SEG17 value Each time you press the button will be selected in rotation SEG16 SEG17 14 Setting Dry mode Press Mode button to be change to Dry mode in the OFF status 15 Setting SEG18 S...

Page 27: ...tting an indoor unit address MAIN RMC 1 Check whether power is supplied or not When the indoor unit is not plugged in there should be additional power supply in the indoor unit 2 Before installing the...

Page 28: ...for the condition of each installation location 1 Check whether power is supplied or not When the indoor unit is not plugged in there should be additional power supply in the indoor unit 2 Set the ins...

Page 29: ...es installation option Detailed Option No 02XXXX 1XXXXX 2XXXXX 3XXXXX Option SEG1 SEG2 SEG3 SEG4 SEG5 SEG6 Explanation PAGE Mode Use of robot cleaning Use of external room temperature sensor Minimizin...

Page 30: ...t 5 Disuse 0 Default value 2 channel 2 1 2 C Disuse 1 Oil return or Noise decreasing in defrost mode 3 channel 3 2 5 C Disuse 4 channel 4 3 Default 5 Use 6 4 2 C Use 6 5 5 C Use 6 Advanced function Co...

Page 31: ...Mode Select switch MCM C200 on the outdoor unit and fix it as Cool mode If Fan is set to off for cooling only indoor unit by setting the SEG9 3 or SEG15 3 you need to use an external sensor or wired r...

Page 32: ...ies installation option Detailed Option No 02XXXX 1XXXXX 2XXXXX 3XXXXX Option SEG1 SEG2 SEG3 SEG4 SEG5 SEG6 Explanation PAGE MODE Use of Auto Change Over for HR only in Auto mode When setting SEG3 Sta...

Page 33: ...min 9 Use 9sec A Use 10sec B C D E F Option SEG13 SEG14 SEG15 SEG16 SEG17 SEG18 Explanation Set to variable breeze Control variables when using hot water external heater Indication and Details Indicat...

Page 34: ...EG18 0 Hot water heater is turned on at the same time as the heating thermostat is on and turned off when the heating thermostat is off e g 2 Setting 02 series SEG15 2 Setting 05 series SEG18 A Room t...

Page 35: ...an indoor unit address setting option set the SEG3 as A When changing a digit of indoor unit installation option set the SEG3 as 2 Ex When setting the buzzer control into disuse status Option SEG1 SE...

Page 36: ...Static Pressure mmAq Option code for indoor unit 0 SP 3 010054 1C50D1 202D2D 331204 010054 1C50F1 203838 331203 010054 1C548D 204747 331201 3 SP 6 010054 1C5453 202D2D 331204 010054 1C5447 203838 3312...

Page 37: ...1 Check the following Strength of the installation site Tightness of pipe connection to detect gas leak Electric wiring connection Heat resistant insulation of the pipe Drainage Grounding conductor co...

Page 38: ...va in sensor Short or Open Error on Eva out sensor Short or Open Discharge sensor error Short or Open E122 E123 E126 Indoor fan error E154 Error on outdoor temperature sensor Short or Open Error on co...

Page 39: ...tion 6th detection High pressure sensor is detached Low pressure sensor is detached Outdoor unit copression ration error Outdoor sump down_1 prevetion control Compressor down due to low pressure senso...

Page 40: ......

Reviews: