38
English
Appendix
Troubleshooting
Detection of errors
•
If an error occurs during the operation, an LED flickers and the operation is stopped except the LED.
•
If you re-operate the air conditioner, it operates normally at first, then detect an error again.
LED Display
•
If you turn off the air conditioner when the LED is flickering, the LED is also turned off.
•
If you re-operate the air conditioner, it operates normally at first, then detect an error again.
•
When E108 error occurs, change the address and reset the system.Ex.) When address of the indoor unit #1 and #2
are set as 5, address of the indoor unit #1 will become 5 and indoor unit #2 will display E108, A002.
Abnormal condition
Error
code
LED Display
•
Error on indoor temperature sensor (Short or Open)
E121
•
Error on Eva-in sensor (Short or Open)
•
Error on Eva-out sensor (Short or Open)
•
Discharge sensor error (Short or Open)
E122
E123
E126
•
Indoor fan error
E154
•
Error on outdoor temperature sensor (Short or Open)
•
Error on cond sensor
•
Error on discharge sensor
Other outdoor unit sensor error that is not on the above list
E221
E237
E251
•
When there is no communication between the
indoor∙outdoor units for 2 minutes
•
Communication error received from the outdoor unit
•
3 miniute tracking error on outdoor unit
•
Communication error after tracking due to unmatching
number of installed units
•
Error due to repeated communication address
•
Communication address not confirmed
Other outdoor unit communication error that is not on the
above list
E101
E102
E202
E201
E108
E109
Self diagnosis error display
•
Error due to opened EEV (2nd detection)
•
Error due to closed EEV (2nd detection)
•
Eva in sensor is detached
•
Eva out sensor is detached
•
Thermal fuse error (Open)
E151
E152
E128
E129
E198
Appendix
Summary of Contents for AE071MNMPEH