28
Wiring
Power Cable Specifications
1 phase
Outdoor unit
Rated
Voltage Range
MCA
MFA
Hz
Volts
Min
Max
Min. Circuit Amps.
Max. Fuse Amps.
AE090JXYDEH
50
220-240
198
264
22 A
27.5 A
AE120JXYDEH
50
220-240
198
264
28 A
35 A
AE140JXYDEH
50
220-240
198
264
30 A
37.5 A
AE160JXYDEH
50
220-240
198
264
32 A
40 A
f
f
The power cable is not supplied with Air to water heat pump.
f
f
Supply cords of parts of appliances for outdoor use shall not be lighter than polychloroprene sheathed flexible cord (Code
designation IEC:60245 IEC 57 / CENELEC:H05RN-F)
f
f
This Equipment complies with IEC 61000-3-12.
Indoor Unit
Load
Power supply
Power cable
MAX. length
Type GL
mm
2
,wires
m
A
MIM-E03AN
No Heater
(Water Pump, Valve, Wired RMC)
1Ø, 220-240V,
50Hz
1.5 / 3
<10m
10
2.5 / 3
10m<L<20m
10
Booster Heater (3kw)
4.0 / 3
<10m
20
6.0 / 3
10m<L<20m
20
Booster Heater (~3kw)
+ Backup Heater (~3kw)
6.0 / 3
<10m
40
8.0 / 3
10m<L<20m
40
f
f
The Power cable is not supplied with the heat pump.
f
f
For power cable, use the grade H05RN-F materials in 1Ø system.
f
f
If you connect Backup Heater at separated power cable, you can reduce wire size. (Please refer to control kit installation
manual)
EHS MONO_ODU_IM_05387A-01_BOOK.indb 28