 18  

EB 9527-2 EN

User interface

Liquid density 

in m³

Density of medium at 1 bar (abs) and boiling temperature. To improve the accuracy of the in

-

dicated filling level, enter the liquid density at operating conditions. In this case, the operat

-

ing pressure density must be entered and changed manually (see [Operating pressure]). This 
makes the filling level reading more precise.

Standard gas density 

in m³

Gas density at 1 bar (abs) and 15 °C. The current values for liquid density, gas density in the 
tank, and gas density in the low-pressure pipe are automatically converted and displayed.

Gas density in tank

 and 

Gas density in low-pressure pipe 

in m³

 

Details on gas column correction

Gas density in the tank depends on the nominal pressure and assumed temperature in the 
tank. Gas density in the low-pressure pipe depends on the nominal pressure and assumed 
temperature in the pipe.

Note:

The gas density in the tank and in the low-pressure pipe are required for gas column 

correction of the content reading. If no correction is required, set both densities to 0.

Mixture density 

in m³

Mixture density refers to the density when filling the tank. The operating filling limit is derived 
from this. It is automatically calculated on entering the liquid density.

Summary of Contents for Media 6

Page 1: ...EN Firmware TROVIS VIEW 4 Media 6 V3 10 3 19 Translation of original instructions Electronics from SAMSON Edition February 2016 TROVIS VIEW 4 Software for Media 6 Media 6 Differential Pressure Meter...

Page 2: ...if not avoided will result in death or seri ous injury WARNING Hazardous situations which if not avoided could result in death or seri ous injury NOTICE Property damage message or mal function Note A...

Page 3: ...urement differential pressure mea surement level measurement in transportation vehicles 25 3 2 1 Flow rate measurement 26 3 2 2 Counting flow rate measurement 29 3 2 3 Differential pressure measuremen...

Page 4: ...4 EB 9527 2 EN...

Page 5: ...Media 6 device for example editing plant texts saving and printing configuration data Almost the entire configuration of a Media 6 device can be performed using the software The user level set to Main...

Page 6: ...00 or higher are not compatible with earlier versions e g firmware version 2 30 2 Communication with Media 6 Differential Pressure and Flow Meter To establish communication between the software and t...

Page 7: ...he settings needed for communication with a Media 6 device Identification General data Tank Medium Maintenance Certificates and approvals Operation 3 1 Liquid level measurement By default all settings...

Page 8: ...ification Type Media 6 Differential Pressure Meter Type 5006 Version Firmware version Addition Identifier for different versions Serial no Serial number of the connected Media 6 device 3 1 2 General d...

Page 9: ...A1 in Enter the value in the range between 0 and 100 A blinking bar graph on the display indicates that the adjusted value has been exceeded with a max contact or the value has fallen below the adjus...

Page 10: ...to calculate tank characteristic A default set of data with predetermined values is available in the tank database Load these data and overwrite them with the corresponding tank geometry data and sett...

Page 11: ...ur entries Cylinder upright Cylinder horizontal Ball Characteristic mode Define tank geometry by selecting the corresponding entry Shape of tank bottom Drop down list with five entries Flat head Toris...

Page 12: ...t 20 mA corresponds to the tank MCN or to the gauge pipe marker SCN Select from toggle field Max tank content MCN Tank content up to overflow gauge pipe SCN Permissible filling limit in Geometric volu...

Page 13: ...EB 9527 2 EN 13 User interface...

Page 14: ...14 EB 9527 2 EN User interface 3 1 4 Medium Medium The data for a maximum of four media can be entered...

Page 15: ...to Medium 4 Medium database General medium data Tank pressure Density calculations Densities Operating filling limit hazard warning Calculated values Medium database Load data You can load and modify...

Page 16: ...emperature of the tank This value depends on the tank material operating temperature and the process medium Tank pressure Additional pressure Operating pressure Unit of Operating pressure Additional p...

Page 17: ...nsity No No values need to be entered in Gas density in the tank and Gas density in the low pressure pipe When By preset pressure is selected Min differential pressure Max differential pressure Final...

Page 18: ...ressure pipe are automatically converted and displayed Gas density in tank and Gas density in low pressure pipe in m Details on gas column correction Gas density in the tank depends on the nominal pre...

Page 19: ...g the tank Calculated values Reading of the previously entered value and the automatically calculated value It cannot be edited and is only shown on the software Max tank content MCN Entered in m Tank...

Page 20: ...20 EB 9527 2 EN User interface Save The data can be saved to a file txt e g filling level_01 txt and processed on a computer using other standard software...

Page 21: ...es e g error status sum of error codes are shown and can be reset Other maintenance data Measuring range reading of the connected Media 6 device Reset Restart the Media 6 device This activates changed...

Page 22: ...Information on the connected Media 6 device concerning certificates and approvals Ex certification Indicates whether the connected Media 6 device is approved for use in hazardous areas Oxygen Indicate...

Page 23: ...ontent in Differential pressure Current differential pressure in mbar Max tank content MCN in Tank content up to overflow gauge pipe SCN in Tank content up to Operating filling limit UCW in Min differ...

Page 24: ...Off Limit switch A2 State of limit switch A2 On Off Tap position State of equalizing valve between the and measuring lines Only vis ible if the Equalizing valve open signal Yes see section 3 1 2 on p...

Page 25: ...lling level in tank truck can also be selected The user level is password protected samson for first installation TROVIS VIEW 4 3 20 and higher DURCHFLUSS after update TROVIS VIEW 4 before 3 20 More d...

Page 26: ...r the data required for flow rate measurement Flow rate is visible together with its associated parameters Medium density Density Rho in kg m Enter the medium density for the operating conditions Flow...

Page 27: ...ed or changed data to the database General medium data Medium identifier Unit Medium identifier A maximum of 8 characters can be entered to describe the medium The text appears in up per case letters...

Page 28: ...on the display of the Media 6 device The unit selected in this case relates to the previous Pressure parameter A drop down list contains the units mbar bar kPa psi mm H2O cm H2O m H2O in H2O Calculate...

Page 29: ...ow rate mode is visible together with its associated parameters Besides the parameters entered in Flow rate additional data in Flow rate specifications and Calculated values are required Count Select...

Page 30: ...of counts Max 99 999 999 reading Maximum recordable number of counts At 100 flow rate and the adjusted count the min interval until counter overflow can be deduced Max recordable counts Max 99 999 999...

Page 31: ...he required data Differential pressure is visible together with its associated parameters Differential pressure specifications Min differential pressure Max differential pressure Unit Min differential...

Page 32: ...cifications Additional pressure Additional pressure Yes No When Yes is selected enter the operating pressure and select the corresponding unit from the drop down list mbar bar kPa psi mm H2O cm H2O m...

Page 33: ...lder enter the required data See details in section 3 1 on page 7 In addition to the details weight details listed in General data are required General data Tank truck Permissible total weight Own wei...

Page 34: ...an calibration Menu bar Device Calibration Zero and span calibration Run Zero and span are calibrated Note To be able to perform the calibration in the TROVIS VIEW 4 software refer to u EB 9527 3 for...

Page 35: ...in the online mode In this case communication is established per manently between the Media 6 device and TROVIS VIEW All the configuration and operat ing data are transferred cyclically from the Medi...

Page 36: ...otection at the selector switch on the Media 6 device front left on the housing Set slider switch 4 to OFF see write protection in u EB 9527 3 Menu bar Device Write To write data to the Media 6 device...

Page 37: ...ent is 1 5 The SAMSON memory pen can also be used to exchange data between TROVIS VIEW 4 and the Media 6 device The memory pen serves as a data carrier and is able to load and store data from the Medi...

Page 38: ...38 EB 9527 2 EN...

Page 39: ...EB 9527 2 EN 39...

Page 40: ...SAMSON AG MESS UND REGELTECHNIK Weism llerstra e 3 60314 Frankfurt am Main Germany Phone 49 69 4009 0 Fax 49 69 4009 1507 samson samson de www samson de EB 9527 2 EN 2016 08 18 English...

Reviews: