User interface
Static column
[H] in m
Max. possible liquid column. This corresponds to the inside length (horizontal tank) or inside
height (upright tank). The value is automatically calculated.
Total volume
[V] in m³
Corresponds to the geometric tank volume (gross useable tank volume in m³). The value is
automatically calculated, provided it has not been entered (existing data).
[Tank measuring line]
Length/height
[Hs] in m
Length of measuring line or pipe socket below the tank. Input 0.000 to 5.000 m.
[Reference volume (MCN = max. capacity nominal, SCN = safe capacity nominal)]
The volume at 20 mA corresponds to the tank MCN or to the gauge pipe marker SCN.
Select from toggle field:
−
Max. tank content (MCN)
−
Tank content up to overflow/gauge pipe (SCN)
Permissible filling limit
in %
Geometric volume up to the overflow in relation to the geometric tank capacity in percent;
e.g. 95 %.
Permissible height
[hperm] in m
Permissible height up to the gauge pipe or overflow.
Permissible volume
[Vperm.] in m³
Permissible volume. Corresponds to 'Total volume x [Permissible filling limit/100'.
Note:
If one of the values for filling limit, height, or volume is changed, the other two values
are automatically recalculated.
[Characteristic]
Indicates the tank characteristic, taking into account the tank geometry. The pairs of values
consist of the tank volume V in m³ and the associated tank height H in mm.