16
EB 9527-2 EN
User interface
[
Save data
Save newly entered or changed tank data to Media database.
[General medium data]
−
Medium identifier
−
Unit
−
Shrink factor
Medium identifier
A maximum of 8 characters can be entered to describe the tank content (stored medium). The
text appears in upper-case letters on the display of the Media 6 device.
Unit
· Drop-down list with six entries
−
m³, %, kg, L, ft³, lbs
Shrink factor
Enter the shrink factor valid at the operating temperature of the tank. This value depends on
the tank material, operating temperature, and the process medium.
[Tank pressure]
−
Additional pressure
−
Operating pressure
−
Unit of 'Operating pressure'
Additional pressure
· Yes/No
Select 'Yes' to show 'Operating pressure' under PTANK on the display of the Media 6 device.
Operating pressure
in bar
Enter the actual absolute pressure applied to the tank (usually the air pressure).
Unit of 'Operating pressure'
· Drop-down list with eight entries
−
mbar, bar, kPa, psi, mm H
2
O, cm H
2
O, m H
2
O, in H
2
O
[Density calculations]
When 'By medium data' is selected
−
Data logging
−
Gas column correction
Data logging
· By medium data/By preset pressure