94
EB 8387-5 EN
Appendix
Error codes –
Recommended action
Condensed state message active, when prompted,
Err
appears.
When fault alarms exist, they are displayed here.
53
Initialization time
exceeded
(initialization time >)
Initialization cycle takes too long.
•
No pressure in supply line or pneumatic leakage
•
Supply air failure during initialization
Status classification
[Maintenance required]
Recommended action Check attachment and air supply line. Re-initialize the positioner.
54 Initialization – Forced
venting
1.
A forced venting function is installed (Code 45 = 'YES') and has not
been connected or not properly. As a result, actuator pressure cannot
build up. The alarm is generated when you attempt to initialize the posi-
tioner.
2.
If you attempt to initialize the positioner from the fail-safe position
(SAFE).
Status classification
[Maintenance required]
Recommended action
1.
Check connection and supply voltage of forced venting.
Code
45
HIGH/LOW
2.
Set the
MAN
mode in Code
0
. Re-initialize the positioner.
55
Transit time not
reached
(transit time <)
Actuator transit times detected during initialization are so short that opti-
mal positioner tuning is impossible.
Status classification
[Maintenance required]
Recommended action Install a signal pressure restriction as described in section 5.
56
Pin position
Initialization canceled because selected NOM and SUB initialization
modes require the pin position to be entered.
Status classification
[Maintenance required]
Recommended action Enter pin position over Code
4
and rated travel/angle over Code
5
.
Re-initialize the positioner.
Summary of Contents for 3731-5
Page 71: ...EB 8387 5 EN 71...
Page 102: ...102 EB 8387 5 EN...
Page 103: ...EB 8387 5 EN 103...
Page 104: ...104 EB 8387 5 EN...
Page 105: ...EB 8387 5 EN 105...
Page 106: ...106 EB 8387 5 EN...
Page 107: ...EB 8387 5 EN 107...
Page 110: ...110 EB 8387 5 EN...
Page 111: ...EB 8387 5 EN 111...