EB 8387-5 EN
89
Appendix
Code
no.
Parameter
– Readings/
values [default setting]
Description
48* d6 Condensed state
Read only
Condensed state, made up from the individual states.
OK OK
C
Maintenance required
CR
Maintenance demanded
b
Maintenance alarm
I
Function check
d7 Reference test
Start reference test (for EXPERTplus tests drive signal y steady-
state (d1) and drive signal y hysteresis (d2))
The reference test can only be activated in manual mode as the
valve moves through its entire travel range.
FF parameters
F0 Firmware version for
communication
Read only
F1 Binary input
Read only
0
Active
1
Not active
F3
Simulation PV
Activation of simulation mode
Positioner (AO)
A0 Target Mode
Target operating mode
A1 Actual Mode
Read only
Current operating mode
A2 CAS_IN Value
Read only
Analog set point, adopted from an upstream function block
(value)
A3 CAS_IN Status
Read only
Analog set point, adopted from an upstream function block
(status)
A4 SP Value
Read only
Set point w (value)
A5 SP Status
Read only
Set point w (status)