EB 8387-5 EN
59
Operating the positioner
Start initialization:
1.
Turn until Code
0
appears.
Initialization
2. Press
, the code number
0
blinks.
3.
Turn until Init appears. Press
. The
fail-safe position setting
AtO
or
AtC
is dis
-
played.
Fail-safe position
reading
4.
Keep pressed down for six seconds.
Initialization starts after the progress
indication has stopped.
Progress until
initialization starts
The rated travel/angle of rotation is indicated in % after initialization. Code
5
(nominal
range) remains locked. The parameters for travel/angle range start (Code
8
) and travel/an-
gle range end (Code
9
) can also only be displayed and modified in %.
For a reading in mm/°, enter the pin position (Code 4).
Enter the pin position:
1.
Turn until Code
4
appears.
2. Press
, the code number
4
blinks.
3.
Turn to select pin position on lever (see
relevant section on attachment).
4. Press
to confirm. The nominal range is
displayed in mm/°.
mm
Pin position
Default: OFF
7.5.2
Initialization based on nominal range (NOM)
The calibrated sensor allows the effective valve travel to be set very accurately. During initial-
ization, the positioner checks whether the control valve can move through the indicated nom-
inal range (travel or angle) without collision. If this is the case, the indicated nominal range is
adopted with the limits of travel/angle range start (Code 8) and travel/angle range end
(Code 9) as the operating range.
Summary of Contents for 3731-5
Page 71: ...EB 8387 5 EN 71...
Page 102: ...102 EB 8387 5 EN...
Page 103: ...EB 8387 5 EN 103...
Page 104: ...104 EB 8387 5 EN...
Page 105: ...EB 8387 5 EN 105...
Page 106: ...106 EB 8387 5 EN...
Page 107: ...EB 8387 5 EN 107...
Page 110: ...110 EB 8387 5 EN...
Page 111: ...EB 8387 5 EN 111...