82
EB 8387-5 EN
Appendix
Code
no.
Parameter
– Readings/
values [default setting]
Description
3
Enable configuration
[OFF], ON, ESC
Enables changing of data (automatically deactivated when the
rotary pushbutton has not been operated for 120 seconds).
Codes marked with an asterisk (*) can only be read and not
overwritten when their configuration is not enabled.
FF
blinks on the display when the on-site operation is locked over
FF communication.
Similarly, codes can only read over the SSP interface.
4* Pin position
[OFF], 17, 25, 35, 50, 70,
100, 200 mm,
90° with rotary actuators,
ESC
If you select a pin position in
Code 4 that is too small, the
positioner switches to fail-
safe position mode (SAFE)
for reasons of safety.
Follower pin must be mounted in the proper position depending
on the valve travel/opening angle.
Pin position must be entered for nominal (NOM) or substitute
(SUB) initialization.
Pin position
Standard
Adjustment range
Code 4
Code 5
Code 5
17
7.5
3.6 to 17.7
25
7.5
5.0 to 25.0
35
15.0
7.0 to 35.4
50
30.0
10.0 to 50.0
70
40.0
14.0 to 70.7
100
60.0
20.0 to 100.0
200
120.0
40.0 to 200.0
90°
90.0
24.0 to 100.0
5* Nominal range
mm or angle °, ESC
Nominal valve travel or opening angle must be entered for nomi-
nal (NOM) or substitute (SUB) initialization.
The possible adjustment range depends on the pin position from
the table for Code 4.
Code
5
is generally locked until Code
4
is set to '
OFF
', i.e. after a
pin position has been entered, Code
5
can be configured.
Indicates maximum travel/angle reached during initialization
after initialization has been successfully completed.
Summary of Contents for 3731-5
Page 71: ...EB 8387 5 EN 71...
Page 102: ...102 EB 8387 5 EN...
Page 103: ...EB 8387 5 EN 103...
Page 104: ...104 EB 8387 5 EN...
Page 105: ...EB 8387 5 EN 105...
Page 106: ...106 EB 8387 5 EN...
Page 107: ...EB 8387 5 EN 107...
Page 110: ...110 EB 8387 5 EN...
Page 111: ...EB 8387 5 EN 111...