![Samson 3731-5 Mounting And Operating Instructions Download Page 21](http://html1.mh-extra.com/html/samson/3731-5/3731-5_mounting-and-operating-instructions_3899035021.webp)
EB 8387-5 EN
21
Design and principle of operation
3.5
Technical data
Table 10:
Type 3731-5 Positioner
Type 3731-5 Positioner with
F
OUNDATION
TM
fieldbus
Technical data in test certificates additionally apply to explosion-protected devices.
Rated travel
Adjustable
Direct attachment to Type 3277 Actuator:
3.6 to 30 mm
Attachment according to IEC 60534-6 (NAMUR): 3.6 to 200 mm
Rotary actuators (VDI/VDE 3845):
24 to 100° opening angle
Travel range
Adjustable
Within the initialized travel/angle of rotation
Travel can be restricted to
1
/
5
at the maximum.
Bus connection
Fieldbus interface according to
IEC 61158-2, bus powered
Physical Layer Class
113 (without explosion protection) · 111
(explosion-protected version)
Field unit according to
FM 3610 entity and FISCO
Communi-
cation
Fieldbus
Data transmission conforming to
F
OUNDATION
TM
fieldbus
specification
Communication Profile Class: 31 PS, 32 L
Interoperability tested according to Interoperability Test Kit (ITK) 6.2.0
Execution times
AO FB: 30 ms · DI FB: 20 ms · PID: 40 ms
Local
SAMSON SSP interface and serial interface adapter
Software requirements (SSP): TROVIS-VIEW with database module 3731-5
Permissible operating voltage
9 to 32 V DC · Powered by bus line
The limits specified in the examination certificate additionally apply.
Maximum operating current
15 mA
Additional current in case of error 0 mA
Supply air
Type 3731-521, Type 3731-527: 1.4 to 7 bar (20 to 105 psi)
Type 3731-523: 1.4 to 6 bar (20 to 90 psi)
Air quality acc. to
ISO 8573-1
(2004 edition)
Max. particle size and density: Class 4 · Oil content: Class 3
Moisture and water: Class 3
Pressure dew point: at least 10 K below the lowest ambient temperature to be
expected
Signal pressure (output)
0 bar up to supply pressure
Characteristic
Linear/Equal percentage/Reverse equal percentage
Butterfly valve, rotary plug valve or segmented ball valve: Linear/equal
percentage
User-defined: adjustable over operating software
Deviation
≤1 %
Hysteresis
≤0.3 %
Sensitivity
≤0.1 %
Transit time
Up to 240 s separately adjustable for exhaust and supply air by software
Summary of Contents for 3731-5
Page 71: ...EB 8387 5 EN 71...
Page 102: ...102 EB 8387 5 EN...
Page 103: ...EB 8387 5 EN 103...
Page 104: ...104 EB 8387 5 EN...
Page 105: ...EB 8387 5 EN 105...
Page 106: ...106 EB 8387 5 EN...
Page 107: ...EB 8387 5 EN 107...
Page 110: ...110 EB 8387 5 EN...
Page 111: ...EB 8387 5 EN 111...