EB 8387-5 EN
69
Operating the positioner
Perform zero calibration:
1.
Turn until Code
6
appears.
2. Press
, the code number
6
blinks.
3.
Turn until
ZP
appears.
4. Press
to confirm.
5.
Turn until Code
0
appears.
6. Press
, reading:
MAN
, Code
0
blinks.
7.
Turn until
Init
appears. Press
. The
fail-safe position setting
AtO
or
AtC
is dis
-
played.
8. Press
and hold for six seconds.
Zero calibration starts. The positioner
moves the valve to the CLOSED position
and recalibrates the internal electrical zero
point.
Initialization mode
Default: MAX