72
EB 8384-2 EN
Start-up and settings
Enable configuration
Default:
No
Turn
g
Code 3, display: No
Press , Code 3 blinks.
Turn
YES
Press , display:
Enter the pin position and nominal range:
mm
Pin position
Default:
No
mm
Nominal range
(locked when Code 4 = No)
Turn
Code 4
Press , Code 4 blinks.
Turn
Pin position on lever (see relevant
section on attachment)
Press .
Turn
Code 5
Press , Code 5 blinks.
Turn
Nominal travel of the valve
Press .
Select the initialization mode:
Init mode
Default
MAX
Turn
Code 6
Press .
Turn
SUb
Press
to confirm the SUb as the initializa
-
tion mode.
Enter the direction of action:
Direction of action
Default
Turn
Code 7
Press
, Code 7 blinks.
Turn
Direction of action (
ää
/
äæ
)
Press .
Deactivate travel limit:
Travel limitation
Default:
No
Turn
Code 11
Press , Code 11 blinks.
Turn
g
No
Press .
Summary of Contents for 3730-2
Page 19: ...EB 8384 2 EN 19 Design and principle of operation...
Page 109: ...EB 8384 2 EN 109...
Page 110: ...110 EB 8384 2 EN...
Page 111: ...EB 8384 2 EN 111...
Page 112: ...112 EB 8384 2 EN...
Page 113: ...EB 8384 2 EN 113...
Page 114: ...114 EB 8384 2 EN...
Page 115: ...EB 8384 2 EN 115...
Page 116: ...116 EB 8384 2 EN...
Page 117: ...EB 8384 2 EN 117...
Page 118: ...118 EB 8384 2 EN...
Page 119: ...EB 8384 2 EN 119...
Page 120: ...120 EB 8384 2 EN...
Page 121: ...EB 8384 2 EN 121...
Page 122: ...122 EB 8384 2 EN...
Page 123: ...EB 8384 2 EN 123...
Page 124: ...124 EB 8384 2 EN...
Page 125: ...EB 8384 2 EN 125...