EB 8384-2 EN
75
Start-up and settings
Perform zero calibration:
Init mode
Default
MAX
Turn
Code 6
Press , Code 6 blinks.
Turn
ZP
Î
Press INIT key.
Zero calibration starts. The positioner
moves the valve to the CLOSED position
and recalibrates the internal electrical
zero point.
7.8 Reset to default settings
This function resets all start-up and setting
parameters as well as the diagnosis to the
factory default settings (see code list in sec-
tion 14).
Enable configuration:
Turn
g
Code 3, display: No
Press , Code 3 blinks.
Turn
YES
Press , display:
Reset start-up parameters:
Reset
Default:
No
Turn
g
Code 36, display: ••–••–
Press , Code 36 blinks.
Turn
Std
Press .
All start-up parameters as well as the diag-
nosis are reset to their default values.
Code 36 - diAG allows just the diagnosis
data (EXPERTplus) to be reset. Refer to the
Operating Instructions for EXPERTplus valve
diagnostics
u
EB 8389.
Note
Summary of Contents for 3730-2
Page 19: ...EB 8384 2 EN 19 Design and principle of operation...
Page 109: ...EB 8384 2 EN 109...
Page 110: ...110 EB 8384 2 EN...
Page 111: ...EB 8384 2 EN 111...
Page 112: ...112 EB 8384 2 EN...
Page 113: ...EB 8384 2 EN 113...
Page 114: ...114 EB 8384 2 EN...
Page 115: ...EB 8384 2 EN 115...
Page 116: ...116 EB 8384 2 EN...
Page 117: ...EB 8384 2 EN 117...
Page 118: ...118 EB 8384 2 EN...
Page 119: ...EB 8384 2 EN 119...
Page 120: ...120 EB 8384 2 EN...
Page 121: ...EB 8384 2 EN 121...
Page 122: ...122 EB 8384 2 EN...
Page 123: ...EB 8384 2 EN 123...
Page 124: ...124 EB 8384 2 EN...
Page 125: ...EB 8384 2 EN 125...