EB 8384-2 EN
97
Code list
Error codes –
Recommended action
Condensed state message active, when prompted,
Err
appears.
When fault alarms exist, they are displayed here.
58 Zero point
Zero point incorrect
Error can occur when the positioner's attachment position is shifted or when
the valve trim is worn, particularly with soft-sealed plugs.
Status classification
[Maintenance required]
Recommended
action
Check valve and attachment of the positioner. If OK, perform a zero calibra
-
tion over Code 6 (see section 7.7).
We recommend to re-initialize the positioner if zero deviates by more than
5 %.
59 Auto-correction
Errors in the positioner's data section are detected detected by automatic
monitoring and corrected automatically.
Status classification
[No message]
Recommended
action
Automatic
60 Fatal error
Additional indication at
the fault alarm contact
Error in safety-relevant data that cannot be corrected automatically. Possible
cause: EMC disturbances.
The valve is moved to fail-safe position.
Status classification Maintenance alarm (cannot be classified)
Recommended
action
Reset over Code 36 – Std. Re-initialize the positioner.
Summary of Contents for 3730-2
Page 19: ...EB 8384 2 EN 19 Design and principle of operation...
Page 109: ...EB 8384 2 EN 109...
Page 110: ...110 EB 8384 2 EN...
Page 111: ...EB 8384 2 EN 111...
Page 112: ...112 EB 8384 2 EN...
Page 113: ...EB 8384 2 EN 113...
Page 114: ...114 EB 8384 2 EN...
Page 115: ...EB 8384 2 EN 115...
Page 116: ...116 EB 8384 2 EN...
Page 117: ...EB 8384 2 EN 117...
Page 118: ...118 EB 8384 2 EN...
Page 119: ...EB 8384 2 EN 119...
Page 120: ...120 EB 8384 2 EN...
Page 121: ...EB 8384 2 EN 121...
Page 122: ...122 EB 8384 2 EN...
Page 123: ...EB 8384 2 EN 123...
Page 124: ...124 EB 8384 2 EN...
Page 125: ...EB 8384 2 EN 125...