EB 8384-2 EN
Connections
Actuator stem extends FA
(AIR TO OPEN)
Fail-close (for globe and angle valves):
Required supply pressure = Upper bench
range value + 0.2 bar, at least 1.4 bar.
Actuator stem retracts FE
(AIR TO CLOSE)
Fail-open (for globe and angle valves):
For tight-closing valves, the maximum signal
pressure pst
max
is roughly estimated as fol-
lows:
pst
max
=
F +
d² · π · ∆p
[bar]
4 · A
d = Seat diameter [cm]
∆p = Differential pressure across the valve [bar]
A = Actuator diaphragm area [cm²]
F = Upper bench range value of the actuator [bar]
If there are no specifications, calculate as
follows:
Required supply pressure = Upper bench
range value + 1 bar
5.1.3 Signal pressure (output)
The signal pressure at the output (38) of the
positioner can be restricted to 1.4 bar,
2.4 bar or 3.7 bar in Code 16.
The limitation is not activated [No] by de-
fault.
5.2 Electrical connections
Risk of electric shock and/or the formation
of an explosive atmosphere.
For electrical installation, observe the rele-
vant electrotechnical regulations and the ac
-
cident prevention regulations that apply in
the country of use. In Germany, these are
the VDE regulations and the accident pre
-
vention regulations of the employers’ liability
insurance.
The following regulations apply to installa-
tion in hazardous areas: EN 60079-
14: 2008 (VDE 0165, Part 1)
Explosive At-
mospheres – Electrical Installations Design,
Selection and Erection.
Incorrect electrical connection will render the
explosion protection unsafe.
Adhere to the terminal assignment.
Do not undo the enameled screws in or on
the housing.
Do not exceed the maximum permissible val-
ues specified in the EC type examination cer-
tificates when interconnecting intrinsically
safe electrical equipment (U
i
or U
0
, l
i
or I
0
, P
i
or P
0
, C
i
or C
0
and L
i
or L
0
).
Selecting cables and wires
Observe
clause 12 of
EN 60079-14: 2008
(VDE 0165, Part 1) for installation of the in
-
trinsically safe circuits.
DANGER
!
WARNING
!
Summary of Contents for 3730-2
Page 19: ...EB 8384 2 EN 19 Design and principle of operation...
Page 109: ...EB 8384 2 EN 109...
Page 110: ...110 EB 8384 2 EN...
Page 111: ...EB 8384 2 EN 111...
Page 112: ...112 EB 8384 2 EN...
Page 113: ...EB 8384 2 EN 113...
Page 114: ...114 EB 8384 2 EN...
Page 115: ...EB 8384 2 EN 115...
Page 116: ...116 EB 8384 2 EN...
Page 117: ...EB 8384 2 EN 117...
Page 118: ...118 EB 8384 2 EN...
Page 119: ...EB 8384 2 EN 119...
Page 120: ...120 EB 8384 2 EN...
Page 121: ...EB 8384 2 EN 121...
Page 122: ...122 EB 8384 2 EN...
Page 123: ...EB 8384 2 EN 123...
Page 124: ...124 EB 8384 2 EN...
Page 125: ...EB 8384 2 EN 125...