EB 8384-2 EN
91
Code list
Code
no.
Parameter
– Readings/
values [default setting]
Description
26* Limit A1
0.0 to 100.0 %, [2.0 %] of
the operating range, No,
ESC
Alarm A1 responds when the value falls below the limit.
Software limit value A1 is displayed or can be changed in relation to
the operating range.
The setting has no effect when an inductive limit switch is installed.
27* Limit A2
0.0 to 100.0 %, [98.0 %]
of the operating range,
No, ESC
Alarm A2 responds when the value falls below the limit.
Software limit value A2 is displayed or can be changed in relation to
the operating range.
28* Alarm test
Reading direction:
Standard
Turned
[No]
[No]
RUN 1
1 RUN
RUN 2
2 RUN
RUN 3
3 RUN
ESC
ESC
Testing the software limit switch alarm A1 and A2 as well as the fault
alarm contact A3.
If the test is activated, the contact is switched five times.
RUN 1/1 RUN: software limit switch A1 to ≥2.2 mA
RUN 2/2 RUN: software limit switch A2 to ≥2.2 mA
RUN 3/3 RUN: fault alarm contact A3 to ≤1.0 mA
29* Position transmitter x/ix
3)
[
ää
],
äæ
, ESC
Operating direction of the position transmitter: it indicates assign-
ment between travel/angle position and output signal i based on
CLOSED position.
The operating range (see Code 8) of the valve is represented by the
4 to 20 mA signal. Values exceeding or falling below the limits 2.4
to 21.6 mA can be represented.
When a positioner has not been connected (set point less than
3.6 mA), the signal is 0.9 mA and 3.8 mA when the positioner has
not been initialized. When YES is set in Code 32, the position trans
-
mitter issues the value as per Code 30 during initialization or zero
calibration. When No is set in Code 32, 4 mA is issued while cali
-
bration is in progress.
30* Fault alarm ix
3)
HI, LO, [No], ESC
Select if and how faults that cause the fault alarm contact to be
switched are also indicated at the position transmitter output.
HI ix =21.6 ±0.1 mA or LO ix =2.4 ±0.1 mA
Summary of Contents for 3730-2
Page 19: ...EB 8384 2 EN 19 Design and principle of operation...
Page 109: ...EB 8384 2 EN 109...
Page 110: ...110 EB 8384 2 EN...
Page 111: ...EB 8384 2 EN 111...
Page 112: ...112 EB 8384 2 EN...
Page 113: ...EB 8384 2 EN 113...
Page 114: ...114 EB 8384 2 EN...
Page 115: ...EB 8384 2 EN 115...
Page 116: ...116 EB 8384 2 EN...
Page 117: ...EB 8384 2 EN 117...
Page 118: ...118 EB 8384 2 EN...
Page 119: ...EB 8384 2 EN 119...
Page 120: ...120 EB 8384 2 EN...
Page 121: ...EB 8384 2 EN 121...
Page 122: ...122 EB 8384 2 EN...
Page 123: ...EB 8384 2 EN 123...
Page 124: ...124 EB 8384 2 EN...
Page 125: ...EB 8384 2 EN 125...