76 | SAMLEX AMERICA INC.
SECTION 12 |
Remote Parameter Monitoring & Setup Using
USB / RS-232 Serial Communication Protocol
12.6 COMMAND TABLE (Continued)
Command
Format
Command
Example
Meaning
Possible
Response
set/get
relayoverload
on/off
get relayoverload
Return whether the Dry Contact Relay will “close” when overloading.
on
set relayoverload off
Dry Contact Relay will NOT “close” when overloading.
OK
set/get
relayovertemp
on/off
get relayovertemp
Return whether the Dry Contact Relay will “close” when over temperature.
on
set relayovertemp off
Dry Contact Relay will NOT “close” when over temperature.
OK
set/get
relayshort
on/off
get relayshort
Return whether the Dry Contact Relay will “close” when short circuit.
on
set relayshort off
Dry Contact Relay will NOT “close” when short circuit protection.
OK
get/set invmode
offline /online
get invmode
Get Inverter Mode.
offline
set invmode offline
Set Inverter Mode to “offline”.
OK
get/set trantype
synch / unsynch
get trantype
Get Transfer Type.
synch
set trantype synch
Set Transfer Type to “synch”.
OK
get/set olprotect
{n}
get olprotect
Get overload protection (percentage of full load).
110 %
set olprotect 90
Set overload protection percentage to 90 %
OK
get relaystatus
get relaystatus
Get the current status of Bypass Relay.
Inverter
Grid AC
get/set syncfreq
{n.f}
get syncfreq
Get synchronization frequency.
7.0 Hz
set syncfreq 5.5
Set synchronization frequency to 5.5 Hz
OK
get/set ovp
{n.f}
get ovp
Get the OVP setting.
34.0 V
set ovp 29.5
Set the OVP setting to 29.5 V
OK
get/set
ovprecovery
{n.f}
get ovprecovery
Get the OVP Recovery setting.
33.0 V
set ovprecovery 29.5
Set the OVP Recovery setting to 29.5 V
OK
get/set uvp
{n.f}
get uvp
Get the UVP setting.
20.0V
set uvp 20.5
Set the UVP setting to 20.5 V
OK
get/set
uvprecovery
{n.f}
get uvprecovery
Get the UVP Recovery setting.
23.0 V
set uvprecovery 22.5
Set the UVP Recovery setting to 22.5 V
OK
get/set
ovalarm {n.f}
get ovalarm
Get the OV Alarm setting.
33.0 V
set ovalarm 29.5
Set the OV Alarm setting to 29.5 V
OK
get/set
uvalarm {n.f}
get uvalarm
Get the UV Alarm setting.
21.5 V
set uvalarm 22.0
Set the UV Alarm setting to 22.0 V
OK