SAMLEX AMERICA INC. | 75
SECTION 12 |
Remote Parameter Monitoring & Setup Using
USB / RS-232 Serial Communication Protocol
12.6 COMMAND TABLE (Continued)
Command
Format
Command
Example
Meaning
Possible
Response
set rs232speed /
usbvcomspeed {n}
set rs232speed 0
Set RS-232 baudrate to 1200 bps
OK
set rs232speed 1
Set RS-232 baudrate to 2400 bps
OK
set rs232speed 2
Set RS-232 baudrate to 4800 bps
OK
set rs232speed 3
Set RS-232 baudrate to 9600 bps
OK
set rs232speed 4
Set RS-232 baudrate to 14400 bps
OK
set rs232speed 5
Set RS-232 baudrate to 19200 bps
OK
set rs232speed 6
Set RS-232 baudrate to 24000 bps
OK
set rs232speed 7
Set RS-232 baudrate to 28800 bps
OK
set/get
buzfanfault
on/off
get buzfanfault
Return whether the buzzer will “beep” when fan fault.
on
set buzfanfault off
Buzzer will NOT “Beep” when fan fault.
OK
set/get
buzovalarm
on/off
get buzovalarm
Return whether the buzzer will “beep” when OV Alarm.
on
set buzovalarm off
Buzzer will NOT “Beep” when OV Alarm.
OK
set/get
buzuvalarm
on/off
get buzuvalarm
Return whether the buzzer will “beep” when UV Alarm.
on
set buzuvalarm off
Buzzer will NOT “Beep” when UV Alarm.
OK
set/get
buzoverload
on/off
get buzoverload
Return whether the buzzer will “beep” when overloading.
on
set buzoverload off
Buzzer will NOT “Beep” when overloading.
OK
set/get
buzovertemp
on/off
get buzovertemp
Return whether the buzzer will “beep” when over temperature.
on
set buzovertemp off
Buzzer will NOT “Beep” when over temperature.
OK
set/get
buzshort
on/off
get buzshort
Return whether the buzzer will “beep” when short circuit protection.
on
set buzshort off
Buzzer will NOT “Beep” when short circuit protection.
OK
set/get
relayfanfault
on/off
get relayfanfault
Return whether the Dry Contact Relay will “close” when fan fault.
on
set relayfanfault off
Dry Contact Relay will NOT “close” when fan fault.
OK
set/get
relayovalarm
on/off
get relayovalarm
Return whether the Dry Contact Relay will “close” when OV Alarm.
on
set relayovalarm off
Dry Contact Relay will NOT “close” when OV Alarm.
OK
set/get
relayuvalarm
on/off
get relayuvalarm
Return whether the Dry Contact Relay will “close” when UV Alarm.
on
set relayuvalarm off
Dry Contact Relay will NOT “close” when UV Alarm.
OK