68 | SAMLEX AMERICA INC.
11.7 FAN FAILURE ALARM
This alarm / relay based remote signaling is activated if the fan speed reduces or the fan stops.
See Table 11.2 under “Fan Failure” for status of front panel LEDs and LCD messaging resulting from this
condition.
11.8 OVER VOLTAGE ALARM
This alarm / relay based remote signaling is activated when the DC input voltage is higher than the value of
parameter “OV Alarm”. The alarm is reset automatically as follows:
• PSR-1200-24: 0.5V lower than the value of “OV Alarm”
• PSR-1200-48: 1.0V lower than the value of “OV Alarm”
See Table 11.2 under “Over Voltage Alarm” for status of front panel LEDs and LCD messaging resulting from
this condition.
11.9 UNDER VOLTAGE ALARM
This alarm / relay based remote signaling is activated when the DC input voltage is lower than the value of
parameter “UV Alarm”. The alarm is reset automatically as follows:
• PSR-1200-24: 0.5V higher than the value of “UV Alarm”
• PSR-1200-48: 1.0V higher than the value of “UV Alarm”
See Table 11.2 under “Under Voltage Alarm” for status of front panel LEDs and LCD messaging resulting from
this condition.
TABLE 11.1 PROTECTIONS RESULTING IN SHUT DOWN OF INVERTER
Protection and reset
AC GRID
input
conditions
Front panel
LED marked
“AC GRID”
(2, Fig 6.1)
Front panel
LED marked
“INVERTER”
(3, Fig 6.1)
Front
panel LED
marked
“BYPASS”
(4, Fig 6.1)
Front Panel
LED marked
“ALARM”
(5, Fig 6.1)
will be Red
Buzzer
(Parameter
“Buzzer
Setup” set
to Enabled)
Relay for
remote sign-
aling of alarm
(Parameter
Relay Setup
set to
Enabled)
LCD Display
Overload Protection
• Load draws power more
than programmed value of
parameter “OL Protection”
continuously for more than
2 to 3 sec, or
• Load draws Surge Power
higher than 2000W continu-
ously for more than 2 sec
Manual Reset
Inverter will be latched in
shut down condition. To reset,
switch OFF by witching the
3-Position Rocker Switch
(1, Fig 6.1) to OFF position.
Wait for 10 sec and switch
on again
AC Grid
input
available
Green/
Orange
Red
Green
Orange
On
Energized
** Warning **
Over load
protection!!
AC Grid
input not
available
Off
Red
Off
Orange
On
Energized