3.15 SHORE BASED INSTALLATION
3.15.1 Typical Shore Based Installation
Fig. 3.13 illustrates a typical shore based installation
• Battery is connected to the DC input connections through an appropriate fuse to protect the
DC input cables against short circuit
• Battery Temperature Sensor Model EVO-BCTS is installed on the Positive or Negative post of
the battery and connected to the port for the Temperature Sensor
• Supplementary battery charging is being carried out through a solar array and a Charge
Controller connected to the DC input provided for external battery charger.
• AC input to the EVO is fed from the Grid and Generator Panel
• AC output from the EVO is fed to the AC Distribution Panel
• Automatic Generator start/stop is possible as follows:
•
Start operation is initiated by contact closure of the Status Relay (14, Fig 2.1) when
battery voltage drops to the programmed value of the Low Voltage Alarm. Stop
sequence is initiated by contact opening when the battery voltage rises to the pro-
grammed “Reset Value”.
•
Contact closure/opening signal is fed to the optional Generator Auto Start/Stop
Module which in turn feeds required start stop signals to the generator (the generator
should be capable of remote start/stop function).
SECTION 3 |
Installation