TABLE 3.2.2 SIZING OF GRID AND GENERATOR INPUT WIRING AND BREAKERS
(FOR INPUT CURRENT LIMIT PROGRAMMED AT 45A FOR EVO-3012 AND EVO-4024)
Model No. and
Rated Output
Power in In-
verter Mode
(Column 1)
Rated
AC Pass
Through
Current
(See Note
1)
(Column 2)
Rated AC
Charging
Current
(See Note
2)
(Column 3)
Total Rated
AC Input
Current
(Columns
2 +3)
(See Note 3)
(Column 4)
Pro-
grammed
AC Input
Current
Limit
(See Note
4)
(Column 5)
NEC Ampac-
ity = 125% of
Column 5
(See Note 5)
(Column 6)
Conductor
Size Based
on NEC
Ampacity
at Column
6
(See Note
6)
(Column 7)
External
Breaker Size
Based
on NEC
Ampacity at
Column 6
(See Note 7)
(Column 8)
EVO-3012
(3000VA, 25A)
25A
20A
45A
45A
56.25A
AWG #6
60A
EVO-4024
(4000VA, 33A)
33A
29A
62A
TABLE 3.2.3 SIZING OF GRID AND GENERATOR INPUT WIRING AND BREAKERS
(FOR INPUT CURRENT LIMIT PROGRAMMED AT 60A FOR EVO-4024)
Model No. and
Rated Output
Power in In-
verter Mode
(Column 1)
Rated
AC Pass
Through
Current
(See Note
1)
(Column 2)
Rated AC
Charging
Current
(See Note 2)
(Column 3)
Total Rated
AC Input
Current
(Columns
2 +3)
(See Note 3)
(Column 4)
Pro-
grammed
AC Input
Current
Limit
(See Note
4)
(Column 5)
NEC Ampac-
ity = 125% of
Column 5
(See Note 5)
(Column 6)
Conductor
Size Based
on NEC
Ampacity
at Column
6
(See Note
6)
(Column 7)
External
Breaker
Size
Based
on NEC
Ampacity at
Column 6
(See Note 7)
(Column 8)
EVO-4024
(4000VA, 33A)
33.33A
29A
62.33A
60A
75A
AWG #4 or
2 x AWG #6
80A
NOTES FOR TABLES 3.2.1, 3.2.2 and 3.2.3 - SIZING OF GRID AND GENERATOR INPUT
WIRING AND BREAKERS
1) Column 2 indicates the Rated AC Pass Through Current when in Charger / Pass
Through Mode (value of this current = Rated AC Output Current in Inverter Mode).
2) Column 3 indicates the Rated AC Side Charging Current in Charger / Pass Through
Mode.
3) Column 4 indicates the total Rated AC Input Current which is the sum of the Rated
AC Pass Through Current (Column 2) and the Rated AC Side Charging Current
(Column 3).
4) Column 5 indicates the Programmed AC Input Current Limit. The value of this
current is programmable using the optional Remote Control Model EVO-RC (See
Appendix A under Group 2 Parameter Setup for Input Settings-"Max Current").
Appropriate value can be programmed to match the available capacity of the Grid
input AC Branch Circuit or the rated capacity of the Generator. Default value for all
the 4 models is 30A.
5) Column 6 indicates NEC Ampacity based on which the wiring conductor size
(Column 7) is determined. This NEC Ampacity is not less than 125% of the
Programmed AC Input Current Limit (Column 5) - Refer to NEC-2014 (National