4 | SAMLEX AMERICA INC.
mm
2
). See Tables 1.1(a), 1.1 (b) and 1.1 (c) for sizing of conductors for AC INPUT circuits
and Table 1.2 for sizing of conductors for AC OUTPUT circuits.
7.
Over current protection (AC Breakers) for the AC input / output circuits has NOT been
provided and has to provided by the installer / user. See guidelines at Tables 1.1(a), 1.1
(b) and 1.1 (c) for sizing of breakers for AC INPUT circuits and Table 1.2 for sizing of
breakers for AC OUTPUT circuits. National and Local Electrical Codes will supersede
these guidelines.
8.
The battery terminals are intended for field connection using Copper conductors that
are sized based on 90°C and are LARGER than AWG #1(42.4 mm
2
). See Tables 1.3(a)
and 1.3(b) for recommended sizes for installation in free air and conduit respectively.
9.
Over current protection (fuse) for battery and External Charger circuits has NOT been
provided and has to provided by the installer / user. See guidelines at Tables 1.3(a) and
1.3(b) for recommended sizes for installation in free air and conduit respectively. Na-
tional and Local Electrical Codes will supersede these guidelines.
10. Tightening torques to be applied to the wiring terminals are given in Table 1.4.
11. This unit has been provided with integral protections against overloads.
12. WARNING! To reduce risk of electric shock and fire:
•
Installation should be carried out by certified installer and as per Local and National
Electrical Codes.
•
Do not connect to circuit operating at more than 150 Volts to Ground.
•
Do not connect to AC Load Center (Circuit Breaker Panel) having Multi-wire Branch
Circuits connected .
•
Both AC and DC voltage sources are terminated inside this equipment. Each circuit
must be individually disconnected before servicing.
•
Do not remove cover. No user serviceable part inside. Refer servicing to qualified
servicing personnel.
•
Do not mount in zero clearance compartment.
•
Do not cover or obstruct ventilation openings.
•
Fuse(s) should be replaced with the same type and rating as of the original installed
fuse(s).
13. WARNING! Risk of electric shock. Use only those GFCIs that are listed at Table 1.5.
Other types may fail to operate properly when connected to this unit.
14. GROUNDING: The Grounding symbol shown below is used for identifying only the field
wiring equipment-grounding terminal. However, this symbol is usable with the circle
omitted for identifying various points within the unit that are bonded to Ground.
Grounding Symbol /
Déf
aut à la terre
15. Precautions When Working With Batteries.
•
Batteries contain very corrosive diluted Sulphuric Acid as electrolyte. Precautions
should be taken to prevent contact with skin, eyes or clothing. Wear eye protection.
•
Batteries generate Hydrogen and Oxygen during charging resulting in evolution of
SECTION 1 |
Safety Instructions & General Information
Summary of Contents for Evolution EVO-2212
Page 89: ...SAMLEX AMERICA INC 89 Notes ...
Page 90: ...90 SAMLEX AMERICA INC Notes ...
Page 91: ...SAMLEX AMERICA INC 91 Notes ...
Page 133: ...SAMLEX AMERICA INC 41 APPENDIX A Notes ...
Page 134: ...42 SAMLEX AMERICA INC APPENDIX A Notes ...