96 | SAMLEX AMERICA INC.
When the contacts in the BMS close, Pins 4 and 5 of the RJ-45 Jack (6, Fig 2.1) will be shorted.
The following actions will be activated:
•
EVO in Charging Mode:
Charging will stop (charging current will be reduced to 0A).
The 2
nd
line of the Charging Mode Screens shown in the Menu Map for Charging Mode
Screens (Fig 3.7 in EVO-RC-PLUS Manual) will show "Charger Off by BMS" as shown in
the example below for Screen No. 1 for EVO-1212F:
E V O - 1 2 1 2 F
C h a r g i n g
C h a r g e r O f f
b y B M S
B a t t :
1 2 . 0 0 V
0 . 0 A
E x t e r n a l :
0 . 0 A
Screen
No. 1
For more details, refer to Section 3.6.8 and Fig 3.7 of EVO-RC-PLUS Manual.
•
EVO in Inverting Mode:
Inverting will stop. EVO
TM
will go to Standby Mode. The right
half of the 1st Line of the Standby Mode Screens shown in the Menu Map for Standby
Mode Screens (Fig 3.1 in EVO-RC-PLUS Manual) will show “Inv stop by BMS” in 2
consecutive displays - first “Inv stop” and then “by BMS” as shown in example below for
EVO-1212F:
"Inv stop" for 2 sec
"by BMS" for 2 sec
E V O - 1 2 1 2 F
I n v S t o p
O u t p u t :
0 . 0 0 V
< 0 . 1 0 A
0 . 0 0 H z
Screen
No. 1
5.13 CHARGER ONLY MODE
In Off-grid DC powered homes, for efficiency consideration, all lighting and other loads /
appliances are normally powered from 12V batteries that are primarily charged through
solar / wind power. Generator backup is used for powering AC to DC battery charger for
charging the batteries during extended periods of cloudy / no wind conditions. To meet this
requirement, the EVO
TM
can be programmed to operate as a battery charger ONLY. Details are
given below
When “Charger Only” Mode is selected (ONLINE MODE: 2=Charger Only), the EVO
TM
will
operate as a battery charger to charge the batteries and pass through the AC input power to
the loads as long as AC input is available (In DC powered homes, 120 VAC pass through will
normally not be used as all the loads will be DC)
When AC input fails, the Inverter Section will NOT be activated and the EVO
TM
will operate in
“Standby Mode” as long as AC input is NOT available. In “Standby Mode”, the EVO
TM
draws
extremely low power from the batteries (< 5W)
For further details, please refer to the following Sections of the EVO-RC Plus Manual:
• Section 4.1.3.1: Screen No. 13 of “Select Parameter Menu Map for Group 1 – CHARGE
CURVE” at Fig 4.2
• Section 4.4.2.13.2: “Charger Only Mode” under ONLINE MODE
SECTION 5 |
Battery Charging in Evolution
TM
Series
Summary of Contents for Evolution EVO-1212F
Page 109: ...SAMLEX AMERICA INC 109 Notes...
Page 110: ...110 SAMLEX AMERICA INC Notes...